11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 70
(1) For main circuit power supply
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications
given in this section.
Servo amplifier
Molded-case circuit breaker (Note 1, 4)
Fuse
Magnetic
contactor
(Note 2)
Frame, rated current
Voltage AC
[V]
Class Current
[A]
Voltage AC
[V]
Power factor
improving reactor is
not used
Power factor
improving reactor is
used
MR-J4-10TM
30 A frame 5 A
30 A frame 5 A
240 T
10
300
S-N10
S-T10
MR-J4-20TM
30 A frame 5 A
30 A frame 5 A
MR-J4-40TM
30 A frame 10 A
30 A frame 5 A
15
MR-J4-60TM
30 A frame 15 A
30 A frame 10 A
20
MR-J4-70TM
30 A frame 15 A
30 A frame 10 A
MR-J4-100TM
(3-phase power
supply input)
30 A frame 15 A
30 A frame 10 A
MR-J4-100TM
(1-phase power
supply input)
30 A frame 15 A
30 A frame 15 A
30
MR-J4-200TM
30 A frame 20 A
30 A frame 20 A
40
S-N20
(Note 3)
S-T21
MR-J4-350TM
30 A frame 30 A
30 A frame 30 A
70
S-N20
S-T21
MR-J4-500TM
50 A frame 50 A
50 A frame 50 A
125
S-N35
S-T35
MR-J4-700TM
100 A frame 75 A
60 A frame 60 A
150
S-N50
S-T50
MR-J4-11KTM
100 A frame 100 A
100 A frame 100 A
200
MR-J4-15KTM
125 A frame 125 A
125 A frame 125 A
250
S-N65
S-T65
MR-J4-22KTM
225 A frame 175 A
225 A frame 175 A
350
S-N95
S-T100
MR-J4-60TM4
30 A frame 5 A
30 A frame 5 A
480 T
10
600
S-N10
S-T10
MR-J4-100TM4
30 A frame 10 A
30 A frame 5 A
15
MR-J4-200TM4
30 A frame 15 A
30 A frame 10 A
25
MR-J4-350TM4
30 A frame 20 A
30 A frame 15 A
35
S-N20
(Note 3)
S-T21
MR-J4-500TM4
30 A frame 20 A
30 A frame 20 A
50
MR-J4-700TM4
30 A frame 30 A
30 A frame 30 A
65
S-N20
S-T21
MR-J4-11KTM4
50 A frame 50 A
50 A frame 50 A
100
S-N25
S-T35
MR-J4-15KTM4
60 A frame 60 A
60 A frame 60 A
150
S-N35
S-T35
MR-J4-22KTM4
100 A frame 100 A
100 A frame 100 A
175
S-N50
S-T50
MR-J4-10TM1
30 A frame 5 A
30 A frame 5 A
240 T
10
300
S-N10
S-T10
MR-J4-20TM1
30 A frame 10 A
30 A frame 10 A
15
MR-J4-40TM1
30 A frame 15 A
30 A frame 10 A
20
Note 1. When having the servo amplifier comply with the IEC/EN/UL/CSA standard, refer to app. 4.
2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less.
3. S-N18 can be used when auxiliary contact is not required.
4. Use a molded-case circuit breaker which has the same or more operation characteristics than our lineup.
Содержание MR-J4 TM Series
Страница 9: ...A 8 MEMO ...
Страница 17: ...8 MEMO ...
Страница 225: ...5 PARAMETERS 5 86 MEMO ...
Страница 295: ...8 TROUBLESHOOTING 8 14 MEMO ...
Страница 439: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Страница 521: ...16 FULLY CLOSED LOOP SYSTEM 16 20 MEMO ...
Страница 578: ...APPENDIX App 41 ...