Parameter
Communication operation and settings
FR-D700 SC EC
6 - 225
Communication specifications
Item
Description
Related
Parameters
Communication protocol
Modbus-RTU protocol
Pr. 549
Conforming standard
EIA-485 (RS485)
—
Number of inverters connected
1 : N (maximum 32 units), setting is 0 to 247 stations
Pr. 117
Communication speed
Can be selected from 4800/9600/19200 and 38400bps
Pr. 118
Control protocol
Asynchronous system
—
Communication method
Half-duplex system
—
Communication
specifications
Character system Binary (fixed to 8 bits)
—
Start bit
1bit
—
Stop bit length
Select from the following three types
No parity, stop bit length: 2 bits
Odd parity, stop bit length: 1 bit
Even parity, stop bit length: 1 bit
Pr. 120
Parity check
Error check
CRC code check
—
Terminator
—
—
Waiting time setting
—
—
Tab. 6-66:
Communication specifications