Communication operation and settings
Parameter
6 - 220
●
Fault data
Refer to section 7.1 for details of alarm description.
쑶
Data
Description
Data
Description
Data
Description
H00
No fault present
H40
E.FIN
HB1
E.PUE
H10
E.OC1
H52
E.ILF
HB2
E.RET
H11
E.OC2
H60
E.OLT
HC0
E.CPU
H12
E.OC3
H70
E.BE
HC4
E.CDO
H20
E.OV1
H80
E.GF
HC5
E.IOH
H21
E.OV2
H81
E.LF
HC7
E.AIE
H22
E.OV3
H90
E.OHT
HC9
E.SAF
H30
E.THT
H91
E.PTC
HF5
E.5
H31
E.THM
HB0
E.PE
—
—
Tab. 6-61:
Fault data
Example
쑴
Fault description display example (instruction code: H74)
I002019E
Fig. 6-115:
Fault example
Previous fault
(H30)
Latest fault
(H10)
For read data = H3010
previous fault ............ THT
latest fault ................. OP1