Selection of operation mode and operation location
Parameter
6 - 192
Switching of command source by external terminal (X67)
In the network operation mode, the command source switching signal (X67) can be used to
switch the start command source and speed command source.
Set "67" to any of Pr. 178 to Pr. 182 to assign the X67 signal to the control terminal.
When the X67 signal is off, the start command source and speed command source are control
terminal.
X67 Signal State
Operation Command Source
Speed Command Source
No signal assignment
According to Pr. 338
According to Pr. 339
ON
OFF
Operation is valid only from external terminal signal.
Tab. 6-47:
Switching of command source by the signal X67
NOTES
The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop
when the terminal is switched during operation.
When the X67 signal is off, a reset via communication is disabled.
Changing the terminal assignment using Pr. 178 to Pr. 182 may affect the other functions.
Please make setting after confirming the function of each terminal.