Current monitoring reference (Pr. 56)
Set the current to be referenced when the current monitor (inverter output current, etc.) is se-
lected for terminal AM display. Set the full scale value when outputting the current monitor from
terminal AM.
●
Set the current value when the voltage output at terminal AM is 10V DC. The analog voltage
output and current value at terminal AM are proportional. (The maximum output voltage is
10V DC.)
Fig. 6-64:
Current monitoring reference
I001165E
10V DC
Setting range of Pr. 56
Rated output current
(initial value)