Parameter
Parameter overview
FR-D700 SC EC
6 - 9
Func-
tion
Parameter
Name
Incre-
ments
Initial
value
Setting
range
Description
Para-
meter
copy
Para-
meter
clear
All
Para-
meter
clear
Refer
to
page
Rel
a
ted
pa
ramet
e
rs
✔
: enabled
—: disabled
Applied motor
71
Applied motor
1
0
0
Thermal characteristics of a stand-
ard motor
✔
✔
✔
1
Thermal characteristics of the Mit-
subishi constant-torque motor
40
Thermal characteristic of Mitsubi-
shi high efficiency standard motor
(SF-HR)
50
Thermal characteristic of Mitsubi-
shi constant torque motor (SF-
HRCA)
3
Standard
motor
Select "offline
auto tuning set-
ting"
13
Constant-
torque motor
23
Mitsubishi
standard
motor SF-JR
4P (
≤
1,5 kW)
43
Mitsubishi
high efficiency
motor
(SF-HR)
53
Mitsubishi
constant-
torque motor
(SF-HRCA)
450
Second applied motor
1
9999
0
Thermal characteristics of a stand-
ard motor
✔
✔
✔
1
Thermal characteristics of the Mit-
subishi constant-torque motor
9999
Second motor is invalid (thermal
characteristic of the first motor
(Pr.71))
Carrier frequency and
Soft-PWM selection
72
PWM frequency
selection
1
1
0–15
PWM carrier frequency can be
changed. The setting displayed is
in [kHz]. Note that 0 indicates
0.7kHz, 15 indicates 14.5kHz.
✔
✔
✔
240
Soft-PWM operation
selection
1
1
0
Soft-PWM invalid
✔
✔
✔
1
When Pr. 72 = "0 to 5", Soft-PWM
is valid.
260
PWM frequency
automatic switchover
1
0
0
PWM carrier frequency is constant
independently of load.
✔
✔
✔
1
Decreases PWM carrier frequency
automatically when load
increases.
Analog input selection
73
Analog input selection
1
1
Terminal 2
input
Polarity reversible
✔
—
✔
0
0–10V
Not used
1
0–5V
10
0–10V
With
11
0–5V
267
Terminal 4 input
selection
1
0
0
Terminal 4 input 0/4 to 20mA
✔
—
✔
1
Terminal 4 input 0 to 5V
2
Terminal 4 input 0 to 10V
Tab. 6-1:
Parameter overview (9)
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......