Operation
Precautions for use of the inverter
FR-D700 SC EC
4 - 5
Checking the inverter operating status by the inverter operation ready completion signal
Operation ready signal (RY signal) is output when the inverter power is on and the inverter be-
comes operative. Check if the RY signal is output after powering on the inverter.
Checking the inverter operating status by the start signal input to the inverter and
inverter running signal
The inverter running signal (RUN signal) is output when the inverter is running (RUN signal is as-
signed to terminal RUN in the initial setting).
Check if RUN signal is output when inputting the start signal to the inverter (forward signal is STF
signal and reverse signal is STR signal). For logic check, note that RUN signal is output for the
period from the inverter decelerates until output to the motor is stopped, configure a sequence
considering the inverter deceleration time.
Checking the motor operating status by the start signal input to the inverter and inverter
output current detection signal
The output current detection signal (Y12 signal) is output when the inverter operates and cur-
rents flows in the motor. Check if Y12 signal is output when inputting the start signal to the in-
verter (forward signal is STF signal and reverse signal is STR signal).
Note that the current level at which Y12 signal is output is set to 150% of the inverter rated cur-
rent in the initial setting, it is necessary to adjust the level to around 20% using no load current
of the motor as reference with Pr. 150 "Output current detection level".
For logic check, as same as the inverter running signal (RUN signal), the inverter outputs for the
period from the inverter decelerates until output to the motor is stopped, configure a sequence
considering the inverter deceleration time.
I001878E
Fig. 4-3:
Ready status and motor running
Power supply
Output frequency
Pr. 13 "Starting frequency"
DC injection
brake operation
Time
DC injection brake
operation point
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
Reset processing
STF
RH
RY
RUN
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......