Operation setting at alarm occurrence
Parameter
6 - 140
Using Pr. 65 you can select the alarm that will cause a retry to be executed. No retry will be made
for the alarm not indicated.
Alarm
Display
for Retry
Name
Parameter 65 Setting
0
1
2
3
4
5
E.OC1
Overcurrent shut-off during acceleration
✔
✔
—
✔
✔
✔
E.OC2
Overcurrent shut-off during constant speed
✔
✔
—
✔
✔
—
E.OC3
Overcurrent shut-off during deceleration or stop
✔
✔
—
✔
✔
✔
E.OV1
Regenerative over voltage shut-off during acceleration
✔
—
✔
✔
✔
—
E.OV2
Regenerative over voltage shut-off during constant speed
✔
—
✔
✔
✔
—
E.OV3
Regenerative over voltage shut-off during deceleration or stop
✔
—
✔
✔
✔
—
E.THM
Motor overload shut-off (electronic thermal relay function)
✔
—
—
—
—
—
E.THT
Inverter overload shut-off (electronic thermal relay function)
✔
—
—
—
—
—
E.BE
Brake transistor alarm detection/Internal circuit error
✔
—
—
—
✔
—
E.GF
Output side earth (ground) fault overcurrent protection
✔
—
—
—
✔
—
E.OHT
External thermal relay operation
✔
—
—
—
—
—
E.PTC
PTC thermistor operation
✔
—
—
—
—
—
E.OLT
Stall Prevention
✔
—
—
—
✔
—
E.PE
Parameter storage device alarm
✔
—
—
—
✔
—
E.ILF
Input phase failure
✔
—
—
—
✔
—
E.CDO
Output current detection value exceeded
✔
—
—
—
✔
—
Tab. 6-27:
Faults selected for retry
NOTES
When terminal assignment is changed using Pr. 190, Pr. 192 and Pr. 197, the other func-
tions may be affected. Make setting after confirming the function of each terminal.
For a retry error, only the description of the first alarm is stored.
When an inverter alarm is reset by the retry function at the retry time, the accumulated data
of the electronic thermal relay function, regeneration converter duty etc. are not cleared.
(Different from the power-on reset.)
Retry is not performed if E.PE (Parameter storage device fault) occurred at power on.
If a fault that is not selected for a retry occurs during retry operation (retry waiting time), the
retry operation stops while the fault indication is still displayed.
b
CAUTION:
When you have selected the retry function, stay away from the motor and machine
unless required. They will start suddenly (after the reset time has elapsed) after
occurrence of an alarm.
When you have selected the retry function, apply CAUTION seals in easily visible
places.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......