Function assignment of external terminals
Parameter
6 - 102
Alarm output signal (ALM)
If the inverter comes to trip, the ALM signal is output. (Refer to section 7.1.)
Fault output 3 (power-off signal) (Y91)
The Y91 signal is output at occurrence of a fault attributable to the failure of the inverter circuit
or a fault caused by a wiring mistake. When using the Y91 signal, set "91 (positive logic)" or "191
(negative logic)" to any of Pr. 190, Pr. 192 or Pr. 197 to assign the function to the output terminal.
I001797E
Fig. 6-52:
Alarm signals
NOTE
The ALM signal is assigned to the ABC contact in the default setting. By setting "99" (posi-
tive logic) or "199" (negative logic) in Pr. 190, Pr. 192 or Pr. 197, the ALM signal can be
assigned to the other signal.
Operation Panel Indication
Name
E.BE
Brake transistor alarm detection
E.GF
Output side earth (ground) fault overcurrent
E.LF
Output phase loss
E.PE
Parameter storage device fault
E.CPU
CPU fault
E.IOH
Inrush current limit circuit fault
Tab. 6-17:
Faults that lead to Y91 signal output
NOTE
At occurrence of output side earth (ground) fault overcurrent (E.GF), overcurrent trip during
acceleration (E.OC1) may be displayed. At this time, the Y91 signal is output.
Inverter alarm occurrence
(output shutoff)
Output
frequency
Reset ON
Time
Reset processing
(about 1s)
ON
ON
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......