Communication operation and settings
Parameter
6 - 240
●
Fault history
Register
Definition
Read/Write
Remarks
40501
Fault history 1
Read/write
Being 2 bytes in length, the data is stored as
"H00
". The error code can be referred to in the
low-order 1 byte.
Performing write using the register 40501 batch-
clears the alarm history. Set any value as data.
40502
Fault history 2
Read
40503
Fault history 3
Read
40504
Fault history 4
Read
40505
Fault history 5
Read
40506
Fault history 6
Read
40507
Fault history 7
Read
40508
Fault history 8
Read
Tab. 6-84:
Fault history
Data
Description
Data
Description
Data
Description
H00
No fault present
H40
E.FIN
HB1
E.PUE
H10
E.OC1
H52
E.ILF
HB2
E.RET
H11
E.OC2
H60
E.OLT
HC0
E.CPU
H12
E.OC3
H70
E.BE
HC4
E.CDO
H20
E.OV1
H80
E.GF
HC5
E.IOH
H21
E.OV2
H81
E.LF
HC7
E.AIE
H22
E.OV3
H90
E.OHT
HC9
E.SAF
H30
E.THT
H91
E.PTC
HF5
E.5
H31
E.THM
HB0
E.PE
—
—
Tab. 6-85:
Fault code list
NOTE
Refer to section 7.1 for details of fault definition.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......