Installation
Enclosure design
FR-D700 SC EC
2 - 11
2.4.2 Inverter
placement
Clearances around the inverter
Always observe the specified minimum clearances to ensure good heat dissipation and ade-
quate accessibility of the frequency inverter for servicing.
Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed
above the inverter should be heat resistant.
I001975E
Fig. 2-9:
Clearances
Ambient temperature and humidity
Clearances (side)
Clearances (front)
Leave enough clearances and take
cooling measures.
In
v
e
rt
er
5cm
5cm
5cm
≥
10cm
≥
10cm
≥
1cm
≥
1cm
x = Measurement
position
In
v
e
rt
er
Temperature:
−
10°C to +50°C
Humidity: 90% RH maximum
≥
1cm
When using the inverters at the
ambient temperature of 40°C or
less, the inver ters can be
installed without any clearance
between them (0cm clearance).
When ambient temperature
exceeds 40°C, clearances
between the inverters should
be 1cm or more (5cm or more
for the FR-D740-120SC or
more).
≥
5cm for the FR-D740-
120SC and more
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......