Parameter
Monitor display and monitor output signals
FR-D700 SC EC
6 - 115
Display set frequency during stop (Pr. 52)
When "100" is set in Pr. 52, the set frequency and output frequency are displayed during stop
and operation respectively. LED of Hz flickers during stop and is lit during operation.
The set frequency displayed indicates the frequency to be output when the start command
is on. Different from the frequency setting displayed when Pr. 52 = "5", the value based on
maximum/minimum frequency and frequency jump is displayed.
Parameter 52
0
100
During running/stop
During stop
During running
Output frequency
Output frequency
Set frequency
Output frequency
Output current
Output current
Output voltage
Output voltage
Alarm display
Alarm display
Tab. 6-20:
Display during running and stop
NOTES
During an error, the output frequency at error occurrence appears.
During MRS, the values displayed are the same as during a stop.