Parameter
Parameter overview
FR-D700 SC EC
6 - 3
Func-
tion
Parameter
Name
Incre-
ments
Initial
value
Setting
range
Description
Para-
meter
copy
Para-
meter
clear
All
Para-
meter
clear
Refer
to
page
Rel
a
ted
pa
ramet
e
rs
✔
: enabled
—: disabled
Motor protection from overheat
(electronic thermal relay function)
9
Electronic thermal
O/L relay
0.01A
Rated
inverter
output
current
0–500A
Set the rated motor current.
✔
✔
✔
51
Second electronic
thermal O/L relay
0.01A
9999
0–500A
Made valid when the RT signal is
on. Set the rated motor current.
✔
✔
✔
9999
Second electronic thermal O/L
relay invalid
561
PTC thermistor
protection level
0.01k
Ω
9999
0.5–30k
Ω
Set the level (resistance value) for
PTC thermistor protection acti-
vates.
✔
—
✔
9999
PTC thermistor protection is
inactive.
DC injection brake
10
DC injection brake
operation frequency
0.01Hz
3Hz
0–120Hz
Set the operation frequency of the
DC injection brake.
✔
✔
✔
11
DC injection brake
operation time
0.1s
0.5s
0
DC injection brake disabled
✔
✔
✔
0.1–10s
Set the operation time of the DC
injection brake.
12
DC injection brake
operation voltage
0.1%
6/4% *
0
DC injection brake disabled
✔
✔
✔
0.1–30%
Set the DC injection brake voltage
(torque).
*
Initial values differ according to
the inverter capacity:
FR-D720S-008SC and 014SC/
FR-D720S-025SC or more,
FR-D740-012SC or more
Starting
frequency
13
Starting frequency
0.01Hz
0.5Hz
0–60Hz
Starting frequency can be set.
✔
✔
✔
571
Holding time at a start
0.1s
9999
0–10s
Set the holding time of Pr. 13
"Starting frequency".
✔
✔
✔
9999
Holding function at stat is invalid.
V/f pattern matching
applications
14
Load pattern selection
1
0
0
For constant torque load
✔
✔
✔
1
For variable-torque load
2
For constant
torque eleva-
tors
at reverse rotation
boost of 0%
3
at forward rota-
tion boost of 0%
Jog operation
15
Jog frequency
0.01Hz
5Hz
0–400Hz
Set the frequency for jog
operation.
✔
✔
✔
16
Jog acceleration/
deceleration time
0.1s
0.5s
0–3600s
Set the acceleration/deceleration
time for jog operation. Set the time
taken to reach the frequency set in
Pr. 20 "Acceleration/deceleration
reference frequency" for accelera-
tion/deceleration time (initial value
is 50Hz).
In addition, acceleration/decelera-
tion time can not be set separately.
✔
✔
✔
Tab. 6-1:
Parameter overview (3)
V/FV
/F
V/F
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......