Basic settings
Simple mode parameter list
FR-D700 SC EC
5 - 7
5.1.4
Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)
Pr.
No.
Name
Initial Value
Setting
Range
Description
1
Maximum frequency
120Hz
0–120Hz
Set the upper limit of the output frequency.
2
Minimum frequency
0Hz
0–120Hz
Set the lower limit of the output frequency.
Example
쑴
You can limit the motor speed. Limit the frequency set by the potentiometer, etc. to 50Hz
maximum. (Set "50" Hz to Pr. 1 "Maximum frequency".)
Fig. 5-5:
Minimum and maximum output frequency
I001100E
Pr. 1
Pr. 18
Clamped at the
maximum frequency
5, 10V
(20mA)
Output
frequency [Hz]
Pr. 2
Frequency
setting
0
(4mA)
Clamped at the
minimum frequency
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......