Special operation
Parameter
6 - 258
I/O signals and parameter setting
Set "40 to 43" in Pr. 128 to perform dancer control.
Set "14" in any of Pr. 178 to Pr. 182 to assign PID control selection signal (X14) to turn the
X14 signal on. When the X14 signal is not assigned, only the Pr. 128 setting makes dancer
control valid.
Input the set point using Pr. 133, then input the measured value signal (dancer roller position
detection signal) across terminal 4 and 5 of the inverter.
When the X14 signal is not assigned, only the Pr. 128 setting makes dancer control valid.
The half-tone screened areas indicate the parameter initial values.
When 100 or larger value is set in any of Pr. 190, Pr. 192 or Pr. 197, the terminal output has
negative logic. (For details, refer to section 6.9.5.)
NOTES
When Pr. 128 = "0" or X14 signal is off, normal inverter operation is performed without
dancer control.
Turning ON/OFF of bit of the terminal, to which X14 signal is assigned through network as
RS485 communication, enables dancer control.
Signal
Terminal
used
Function
Description
Parameter Setting
Input
X14
Depending
on
Pr. 178 to
Pr. 182
PID control
selection
Turn on X14 signal to perform
dancer control.
Set "14" in any of Pr. 178 to
Pr. 182.
4
4
Measured
value input
Input the signal from the dancer
roller detector (measured value
signal).
Pr. 128 = 40, 41, 42, 43
4–20mA .... 0–100%
Pr. 267 = 0
0–5V ......... 0–100%
Pr. 267 = 1
0–10V ....... 0–100%
Pr. 267 = 2
Output
FUP
Depending
on Pr. 190/
192/ 197
Upper limit out-
put
Output to indicate that the meas-
ured value signal exceeded the
maximum value (Pr. 131).
Pr. 128 = 40, 41, 42, 43
Pr. 131
≠
9999
Set "15" or "115" in any of
Pr. 190, Pr. 192 or Pr. 197.
FDN
Lower limit out-
put
Output when the measured value
signal falls below the minimum
value (Pr. 132).
Pr. 128 = 40, 41, 42, 43
Pr. 132
≠
9999
Set "14" or "114" in any of
Pr. 190, Pr. 192 or Pr. 197.
RL
Forward
(reverse) rota-
tion direction
output
Output is "ON" when the output
indication of the parameter unit is
forward rotation (FWD) and
"OFF" when reverse rotation
(REV) or stop (STOP).
Set "16" or "116" in any of
Pr. 190, Pr. 192 or Pr. 197.
PID
During PID con-
trol activated
Turns on during PID control.
Set "47" or "147" in any of
Pr. 190, Pr. 192 or Pr. 197.
SE
SE
Output terminal
common
Common terminal for open col-
lector output terminal.
Tab. 6-91:
I/O signals and parameter setting
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......