Precautions for use of the inverter
Operation
4 - 4
4.1.1
Failsafe of the system which uses the inverter
When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may
not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc.
Although Mitsubishi assures best quality products, provide an interlock which uses inverter sta-
tus output signals to prevent accidents such as damage to machine when the inverter fails for
some reason.
At the same time consider the system configuration where failsafe from outside the inverter,
without using the inverter, is enabled even if the inverter fails.
Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an in-
verter alarm can be detected.
Check by the output of the inverter fault signal
When the fault occurs and trips the inverter, the fault output signal (ALM signal) is output (ALM
signal is assigned to terminal ABC in the initial setting). Check that the inverter functions prop-
erly. In addition, negative logic can be set (on when the inverter is normal, off when the fault oc-
curs).
Interlock Method
Check Method
Used Signals
Refer to
Page
Inverter protective
function operation
Operation check of an alarm contact
Circuit error detection by negative logic
Fault output signal
(ALM signal)
Inverter running
status
Operation ready check signal
Operation ready signal
(RY signal)
Logic check of the start signal and running
signal
Start signal
(STF signal, STR signal)
Running signal
(RUN signal)
Logic check of the start signal and output
current
Start signal
(STF signal, STR signal)
Output current detection signal
(Y12 signal)
Tab. 4-1:
Different output signals of the frequency inverter can be used for interlocks
I001877E
Fig. 4-2:
Contact B-C opens when a fault occurs (initial setting)
Inverter fault occurrence
(trip)
Output
frequency
Reset ON
Time
Reset processing
(about 1s)
ON (no Alarm)
Fault output signal (ALM)
(when output at NC contact)
OFF
ON
OFF
Reset (RES)
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......