External operation
Basic settings
5 - 34
쑶
Example
쑴
Set "40Hz" in Pr. 4 "Multi-speed setting (high speed)" and turn on terminals RH and STF
(STR)-PC to operate.
I001778E
Fig. 5-24:
Operate the inverter by using external signals
Power on
→
operation mode check
For the initial setting, the inverter operates in the
external operation mode "EXT" when powering
on. Check that the operation command
indication is "EXT". If not displayed, press the
PU/EXT key to change to the external "EXT"
operation mode.
If the operation mode still does not change, set
Pr. 79 to change to the external operation mode.
(Refer to section 5.1.6).
Change the Pr. 4 setting to "40.00" (40.00Hz).
(Refer to section 4.3.8 for change of the setting.)
Turn on the high speed switch (RH).
Turn the start switch (STF or STR) on.
40Hz appears (30Hz appears when RM is on
and 10Hz appears when RL is on.)
"RUN" display is lit during forward rotation
operation and flickers during reverse rotation
operation.
Stop
Turn the start switch (STF or STR) off.
The motor stops according to Pr. 8
"Deceleration time".
Operation
Display
Stop
Forward rotation
Reverse rotation
OFF
ON
High speed
Middle speed
Low speed
ON
ON
Forward rotation
Reverse rotation
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......