Simple mode parameter list
Basic settings
5 - 16
Setting
Select General-purpose magnetic flux vector control. (Refer to section 5.1.7.)
Set "11" in Pr. 96 to tune motor constant (R1) without running the motor. It takes approxi-
mately 9s until tuning is completed.
Set the rated motor current (initial value is rated inverter current) in Pr. 9 "Electronic thermal
O/L relay" (refer to page 5-2).
Set the rated voltage of motor (initial value is 200V/400V) in Pr. 83 "Rated motor voltage"
and rated motor frequency in Pr. 84 "Rated motor frequency".
Set Pr. 71 "Applied motor" according to the motor used.
For other settings of Pr. 71, refer to the section 6.7.2.
Motor
Parameter 71
Mitsubishi
Standard motor,
high efficiency motor
SF-JR
3
SF-JR 4P-1.5kW or less
23
SF-HR
43
Others
3
Constant-torque motor
SF-JRCA 4P
13
SF-HRCA
53
Others (SF-JRC, etc.)
13
Other
manufac-
turer's
Standard motor
3
Constant-torque motor
13
Tab. 5-3:
Motor selection