Selection of operation mode and operation location
Parameter
6 - 190
Selection of control source in network operation mode (Pr. 338, Pr. 339)
As control sources, there are the operation command source that controls the signals related to
the inverter start command and function selection and the speed command source that controls
the signals related to frequency setting.
In network operation mode, the commands from the external terminals and communication (PU
connector or communication option) are as listed below.
Operation
Location
Selection
Communication Operation
Command Source (Pr. 338)
0: NET
1: External
Remarks
Communication Speed Command
Source (Pr. 339)
0: NET
1:
Exter-
nal
2:
Exter-
nal
0: NET
1:
Exter-
nal
2:
Exter-
nal
Fixed func-
tion
(Terminal-
equivalent
function)
Running frequency from
communication
NET
—
NET
NET
—
NET
Terminal 2
—
External
—
—
External
—
Terminal 4
—
External
—
External
Selectiv
e function
Pr
. 178 to Pr
. 182 setting
0
RL
Low speed operation com-
mand/remote setting clear
NET
External
NET
External
Pr. 59 = 0
(multi-speeds)
Pr. 59
≠ 0
(remote)
1
RM
Middle-speed operation
command/remote setting
deceleration
NET
External
NET
External
2
RH
High speed operation
command/remote setting
acceleration
NET
External
NET
External
3
RT
Second function selection
NET
External
4
AU
Terminal 4 input selection
—
Combined
—
Combined
5
JOG
Jog operation selection
—
External
7
OH
External thermal relay input
External
8
REX
Fifteen speed selection
NET
External
NET
External
Pr. 59 = 0
(multi-speeds)
10
X10
Inverter operation enable sig-
nal
External
12
X12
PU operation external
interlock
External
14
X14
PID control valid terminal
NET
External
NET
External
16
X16
PU-external operation
switchover
External
18
X18
V/f switching
NET
External
Tab. 6-46:
Writing operation and speed commands (1)
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......