
Control circuit specifications
Wiring
3 - 24
Safety stop function operation
At an internal safety circuit fault, E.SAF or E.CPU is displayed on the operation panel.
SA is displayed on the operation panel when both the S1 and S2 signals are in the open
state without any internal safety circuit fault (E.SAF, E.CPU).
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
N/A denotes a condition where circuit fault does not apply.
For more details, refer to the “FR-D700 SC EC – Safety stop function instruction manual (BCN-
A211508-005)".
Input Power
Input Signal
Internal
Safety
Circuit
Output Signal
Operation State
S1-SC
S2-SC
SAFE
SAFE2
OFF
—
—
—
OFF
OFF
Output shutoff
(Safe state)
ON
Short
Short
No failure
OFF
ON
Drive enabled
Detected
OFF
OFF
Output shutoff
(Safe state)
Open
Open
No failure
ON
ON
Output shutoff
(Safe state)
Detected
OFF
OFF
Output shutoff
(Safe state)
Short
Open
N/A
OFF
OFF
Output shutoff
(Safe state)
Open
Short
N/A
OFF
OFF
Output shutoff
(Safe state)
Tab. 3-16:
Description of Safety stop function operation
b
CAUTION:
To use the safety stop function, connect the FR-D700 SC source-logic safety terminal
models only to a safety relay module. If the FR-D700 sink-logic safety terminal models
and the FR-D700 SC source-logic safety terminal models are connected, the safety
stop function does NOT operate.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......