Parameter
Selection of operation mode and operation location
FR-D700 SC EC
6 - 187
Selects the command source of the PU operation mode (Pr. 551)
Any of the operation panel or PU connector can be specified as the command source in the PU
operation mode.
In the PU operation mode, set Pr. 551 to "2" when executing parameter write, start command or
frequency command during the RS485 communication with PU connector.
The Modbus-RTU protocol cannot be used in the PU operation mode. When using the
Modbus-RTU protocol, set Pr. 551
≠
"2".
When Pr. 551 = "9999", the priorities of the PU control source are: parameter unit (FR-PU04/
FR-PU07) > operation panel.
Pr. 551
Command Source
Remarks
Operation
Panel
Parameter Unit
RS485 Communication
2
—
PU
PU
Switching to NET operation
mode disabled
4
PU
—
NET
9999
(initial value)
PU
PU
NET
Tab. 6-43:
Parameter 551 settings
NOTES
When performing the RS485 communication with the PU connector when Pr. 551 = 9999,
PU mode command source does not automatically change to the PU connector.
When "2" (PU mode PU connector) is set in Pr. 551, the operation mode cannot be switched
to the network operation mode.
Changed setting value is made valid when powering on or resetting the inverter.
The Modbus-RTU protocol cannot be used in the PU operation mode. Select network opera-
tion mode (NET mode command source).
All of the operation mode indicator (
) of the operation panel turns OFF when
command source is not operation panel.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......