Parameter
Motor brake and stop operation
FR-D700 SC EC
6 - 85
When a high power factor converter (FR-HC) is used and automatic restart after instan-
taneous power failure function is made valid.
●
When automatic restart after instantaneous power failure function of both the FR-HC and
inverter is made valid (when avalue other than "9999" is set in Pr. 57 "Restart coasting time"),
set "2" in Pr. 30.
●
Set Pr. 70 to "0%" (initial value).
●
When the FR-HC detects power failure during inverter operation, the RDY signal turns on,
resulting in the motor coasting. Turning the RDY signal off after power restoration, the inverter
detects the motor speed (depends on the Pr. 162 "Automatic restart after instantaneous
power failure selection") and restarts automatically after instantaneous power failure.
Regenerative brake duty alarm output and alarm signal (RBP signal)
●
[RB] appears on the operation panel and an alarm signal (RBP) is output when 85% of the
regenerative brake duty set in Pr. 70 is reached. If the regenerative brake duty reaches
100% of the Pr. 70 setting, a regenerative overvoltage (E.OV1 to E.OV3) occurs. Note that
[RB] is not displayed when Pr. 30 = "0".
●
The inverter does not trip even when the alarm (RBP) signal is output.
●
For the terminal used for the RBP signal output, assign the function by setting "7" (positive
logic) or "107" (negative logic) in any of Pr. 190, Pr. 192 or Pr. 197 "Output terminal function
selection".
I001566E
Fig. 6-40:
Regenerative overload
NOTES
The MRS signal can also be used instead of the X10 signal.
Refer to section 3.6 for connecting the high-duty brake resistor (FR-ABR), brake unit
(FR-BU2), high power factor converter (FR-HC), and power regeneration common converter
(FR-CV).
When terminal assignment is changed using Pr. 178 to Pr. 182, Pr. 190, Pr. 192 or Pr. 197,
the other functions may be affected. Make setting after confirming the function of each
terminal.
b
CAUTION:
The value set in Pr. 70 must not exceed the setting of the brake resistor used.
Otherwise, the resistor can overheat.
Regenerative brake
pre-alarm (RBP)
Time
Ratio of the brake
duty to the Pr. 70
setting (%)
OFF
ON
ON
100%
85%
100%: Overvoltage tripping
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......