Troubleshooting
Causes and corrective actions
FR-D700 SC EC
7 - 13
Operation Panel
Indication
E.BE
FR-PU04
FR-PU07
Br. Cct. Fault
Name
Brake transistor alarm detection/internal circuit error
Description
When a brake transistor alarm has occurred due to the large regenerative energy from the
motor etc., the brake transistor alarm is detected and the inverter trips.
In this case, the inverter must be powered off immediately.
Check point
Reduce the load inertia.
Check that the frequency of using the brake is proper.
Check that the brake resistor selected is correct.
Corrective action
Replace the inverter.
Operation Panel
Indication
E.GF
FR-PU04
FR-PU07
Ground Fault
Name
Output side earth (ground) fault overcurrent protection
Description
The inverter trips if an earth (ground) fault overcurrent flows at start due to an earth
(ground) fault that occurred on the inverter's output side (load side). Whether this protective
function is used or not is set with Pr. 249 "Earth (ground) fault detection at start".
Check point
Check for an earth fault in the motor and connection cable.
Corrective action
Remedy the earth fault portion.
Operation Panel
Indication
E.LF
FR-PU04
FR-PU07
E.LF
Name
Output phase loss
Description
If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during
inverter operation (except during DC injection brake operation and when output frequency
is under 1Hz), inverter stops the output.
Whether the protective function is used or not is set with Pr. 251 "Output phase loss protec-
tion selection".
Check point
Check the wiring (Check that the motor is normal.)
Check that the capacity of the motor used is not smaller than that of the inverter.
Corrective action
Wire the cables properly.
Check the Pr. 251 "Output phase failure protection selection" setting.
Operation Panel
Indication
E.OHT
FR-PU04
FR-PU07
OH Fault
Name
External thermal relay operation
Description
If the external thermal relay provided for motor overheat protection or the internally
mounted temperature relay in the motor, etc. switches on (contacts open), the inverter out-
put is stopped.
Functions when "7" (OH signal) is set to any of Pr. 178 to Pr. 182 "Input terminal function
selection". This protective function does not function in the initial status (OH signal is not
assigned).
Check point
Check for motor overheating.
Check that the value of "7" (OH signal) is set correctly in any of Pr. 178 to Pr. 182 "Input
terminal function selection".
Corrective action
Reduce the load and frequency of operation.
Even if the relay contacts are reset automatically, the inverter will not restart unless it is
reset.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......