Maintenance and inspection
Measurements on the main circuit
FR-D700 SC EC
8 - 11
8.2.3
Measurement of voltages and currents
Since voltages and currents in the primary and secondary side of the inverter include harmonics,
different meters indicate different measured values.
When the inverter-to-motor wiring length is large, especially in the 400V class, large-capacity
models, the meters and CTs may generate heat due to line-to-line leakage current. Therefore,
choose the equipment which has enough allowance for the current rating.
When measuring and indicating the output voltage and output current of the inverter, it is rec-
ommended to utilize the AM-5 terminal output function of the inverter. To do this, assign the re-
quired parameter to the terminal.
When using measuring instruments for the normal frequency range, carry out the measure-
ments as described below.
I002040E
Fig. 8-8:
Examples of measuring points and instruments
P/+ N/–
Input
voltage
Input
current
Output
voltage
Output
current
Power supply
Inverter
Instrument types
To the motor
Moving-iron type
Electrodynamometer type
Moving-coil type
Rectifier type
Single-phase, 230 V
Three-phase, 400 V
* At, As, Vt, Vs, W12, W13 are only for the three-phase power input
specification models.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......