Parameter
Misoperation prevention and parameter setting restriction
FR-D700 SC EC
6 - 163
Restarting method when stop was made by pressing the STOP key from the PU during
external operation ("PS" is displayed)
Operation panel
After the motor has decelerated to a stop, turn off the STF or STR signal.
Press the PU/EXT key to change to the PU operation mode. The PU indication is lit. The
message "PS" is canceled.
Press the PU/EXT key to change to the external operation mode. The EXT indication is lit.
Turn on the STF or STR signal.
Parameter unit (FR-PU04/FR-PU07)
After completion of deceleration to a stop, switch off the STF or STR signal.
Press the EXT key. The message "PS" is canceled.
Switch on the STF or STR signal.
The motor can be restarted by making a reset using a power supply reset or RES signal.
I000027C
Fig. 6-88:
Stop during external operation
NOTE
If Pr. 250 "Stop selection" is set to other than "9999" to select coasting to a stop, the motor
will not be coasted to a stop but decelerated to a stop by the PU stop function during exter-
nal operation.
Time
PU key
STOP key
Operation panel
Speed
STF (ON)
STR (OFF)
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......