Special operation
Parameter
6 - 250
PID control automatic switchover control (Pr. 127)
For a fast system start-up at an operation start, the system can be started up in normal operation
mode only at a start.
When the frequency is set to Pr. 127 "PID control automatic switchover frequency" within the
range 0 to 400Hz, the system starts up in normal operation mode from a start until Pr. 127 is
reached, and then it shifts to PID control operation mode. Once the system has entered PID con-
trol operation, it continues PID control if the output frequency falls to or below Pr. 127.
PID output suspension function (SLEEP function) (SLEEP signal, Pr. 575 to Pr. 577)
The inverter stops operation if the output frequency after PID operation remains at less than the
Pr. 576 setting for longer than the time set in Pr. 575. This function can reduce energy con-
sumption in the low-efficiency, low-speed range.
When the deviation (= set value – measured value) reaches the PID output shutoff cancel level
(Pr. 577 setting – 1000%), while the PID output interruption function is on, the PID output in-
terruption function is canceled and PID control operation is resumed automatically.
While the PID output interruption function is on, the PID output interruption signal (SLEEP) is
output. At this time, the inverter running signal (RUN) is OFF, and the PID control operating si-
gnal (PID) is ON.
For the terminal used for the SLEEP signal output, assign the function by setting "70" (positive
logic) or "170" (negative logic) in Pr. 190, Pr. 192 or Pr. 197.
I001234E
Fig. 6-126:
Automatic switchover to PID control
I001235E
Fig. 6-127:
PID output suspension function (SLEEP function)
Output frequency
Normal
operation
PID control
Time
Reverse action (Pr. 128 = 10)
Less than Pr. 575
Cancel
level
Time
Output frequency
Deviation
Pr. 575 or more
SLEEP period
OFF
ON
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......