Electromagnetic compatibility (EMC)
Wiring
3 - 52
3.7.4
Inverter-driven 400V class motor
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the mo-
tor terminals. Especially for a 400V class motor, the surge voltage may deteriorate the insula-
tion. When the 400V class motor is driven by the inverter, consider the following measures:
●
Rectifying the motor insulation and limiting the PWM carrier frequency according to the
wiring length. For the 400V class motor, use an insulation-enhanced motor.
– Specify the "400V class inverter-driven insulation-enhanced motor".
– For the dedicated motor such as the constant-torque motor and low-vibration motor, use
the "inverter-driven, dedicated motor".
– Set Pr. 72 "PWM frequency selection" as indicated below according to the wiring length.
●
Limiting the voltage rise speed of the frequency inverter output voltage (dU/dT):
If the motor requires a rise speed of 500V/µs or less you must install a filter in the output of
the inverter. Please contact your Mitsubishi dealer for more details.
Wiring Length
≤
50m
50m to 100m
≥
100m
Parameter 72
≤
15 (14.5kHz)
≤
8 (8kHz)
≤
2 (2kHz)
Tab. 3-25:
Setting of Pr. 72 according to the wiring length
NOTE
For details of Pr. 72 "PWM frequency selection", refer to section 6.14.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......