Function assignment of external terminals
Parameter
6 - 96
3-wire type (terminals STF, STR and STOP)
A three-wire type connection is shown below.
The start self-holding selection becomes valid when the STOP signal is turned on. In this case,
the forward/reverse rotation signal functions only as a start signal.
If the start signal (STF or STR) is turned on and then off, the start signal is held and makes a start.
When changing the direction of rotation, turn STR (STF) on once and then off. To stop the in-
verter, turning off the STOP signal once decelerates it to a stop. When using the STOP signal,
set "25" in Pr. 178 to Pr. 182 to assign function.
Fig. 6-49:
3-wire type connection (Pr. 250 = 9999)
I001150E
Fig. 6-50:
3-wire type connection (Pr. 250 = 8888)
I001151E
NOTES
When the JOG signal is turned on to enable jog operation, the STOP signal becomes invalid.
If the MRS signal is turned on to stop the output, the self-holding function is not cancelled.
Forward
rotation
Inverter
Output frequency
Fo
rw
a
rd
rotation
Re
v
e
rse
rot
a
tion
Time
ON
Reverse
rotation start
Stop
ON
ON
ON
ON
Start
Inverter
Output frequency
Time
Forward/
reverse rotation
Fo
rw
a
rd
ro
ta
tion
Re
v
e
rse
rotation
ON
ON
ON
ON
ON
Stop
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......