Frequency setting by analog input (terminal 2, 4)
Parameter
6 - 150
Perform operation by analog input voltage
The frequency setting signal inputs 0 to 5V DC (or 0 to 10V DC) to across the terminals 2-5.
The 5V (10V) input is the maximum output frequency.
The power supply 5V can be input by either using the internal power supply or preparing an
external power supply. Prepare an external power supply to input the power supply 10V. For
the built-in power supply, terminals 10-5 provide 5V DC output.
When inputting 10V DC to the terminal 2, set "0" or "10" in Pr. 73. (The initial value is 0 to 5V.)
Setting "1" (0 to 5V DC) or "2" (0 to 10V DC) in Pr. 267 and a voltage/current input switch in the
"V" position changes the terminal 4 to the voltage input specification. When the AU signal turns
on, the terminal 4 input becomes valid.
Fig. 6-80:
Frequency setting by voltage 0–5V DC
I001182E
Fig. 6-81:
Frequency setting by voltage 0–10V DC
I001884E
Terminal
Inverter Built-in Power Supply
Voltage
Frequency Setting
Resolution
Pr. 73 (terminal 2 input voltage)
10
5V DC
0.1Hz/50Hz
0–5V DC
Tab. 6-29:
Built-in power supply voltage
NOTE
The wiring length of the terminal 10, 2, 5 should be 30m maximum.
Forward rotation
Frequency
setting
0–5V DC
Presetting of set frequency value
using terminal 2 (0–5V DC)
PC
Forward rotation
Frequency
setting
0–10V DC
Presetting of set frequency value
using terminal 2 (0–10V DC)
Voltage input
equipment
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......