Special operation
Parameter
6 - 254
NOTES
If the multi-speed (RH, RM, RL, REX signal) or jog operation (jog signal) is entered with the
X14 signal on, PID control is stopped and multi-speed or jog operation is started.
If the setting is as follows, PID control becomes invalid. Pr. 79 "Operation mode selection" =
6 (switchover mode). When the inverter is at a stop with Pr. 261 "Power failure stop selec-
tion" selected.
Changing the terminal function using any of Pr. 178 to Pr. 182, Pr. 190, Pr. 192 or Pr. 197
may affect the other functions. Make setting after confirming the function of each terminal.
When PID control is selected, the minimum frequency is the frequency set in Pr. 902 and the
maximum frequency is the frequency set in Pr. 903. (Pr. 1" Maximum frequency" and Pr. 2
"Minimum frequency" settings are also valid.)
The remote operation function is invalid during PID operation.
When the control is switched to PID control during normal operation, the frequency com-
mand value calculated by PID operation using 0Hz as standard is used without the fre-
quency during the operation.
Frequency
command
PID set point
Frequency command
during normal operation
PID action
ON
Normal
operation
Normal
operation
PID
operation
Operation when control is switched to
PID control during normal operation
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......