Operation panel
Operation
4 - 16
4.3.8
Change the parameter setting value
Possible faults:
●
"Er1", "Er2", "Er3" or "Er4" is displayed.
– The error indication means:
Er1: Write disable error
Er2: Write error during operation
Er3: Calibration error
Er4: Mode designation error
For details refer to section 7.1.
Example
쑴
Change the Pr. 1 "Maximum frequency" setting from 120Hz to 50Hz.
I001462E
Fig. 4-12:
Setting the maximum output frequency
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until P.1 (Pr. 1) appears.
Press the SET key to show the currently set value.
The initial value "120.0" appears.
Turn the digital dial counter clockwise to change it
to the setting value of "50.00".
Press the SET key to set.
Operation
Display
The parameter number
read previously
appears.
Flicker ... Parameter setting complete!
PU indication is lit.
Turn the digital dial to read another parameter.
Press the SET key to show the setting again.
Press the SET key twice to show the next parameter.
Press the MODE key twice to return the monitor to frequency monitor.
PRM indication is lit.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......