Installation
Enclosure design
FR-D700 SC EC
2 - 9
Explosive, flammable gases
As the inverter is non-explosion proof, it must be contained in an explosion proof enclosure.
In places where explosion may be caused by explosive gas, dust or dirt, an enclosure cannot be
used unless it structurally complies with the guidelines and has passed the specified tests. This
makes the enclosure itself expensive (including the test charges).
The best way is to avoid installation in such places and install the inverter in a non-hazardous
place.
Highland
Use the inverter at the altitude of within 1000m.
If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pres-
sure will deteriorate dielectric strength.
Maximum 1000m above sea level for standard operation. After that derate by 3% for every extra
500m up to 2500m (91%).
Vibration, impact
The vibration resistance of the inverter is up to 5.9m/s
2
at 10 to 55Hz frequency and 1mm am-
plitude for the directions of X, Y, Z axes.
Vibration or impact, if less than the specified value, applied for a long time may make the mech-
anism loose or cause poor contact to the connectors. Especially when impact is imposed re-
peatedly, caution must be taken as the part pins are likely to break.
●
Countermeasures
– Provide the enclosure with rubber vibration isolators.
– Strengthen the structure to prevent the enclosure from resonance.
– Install the enclosure away from sources of vibration.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......