Communication operation and settings
Parameter
6 - 222
●
Inverter status monitor
The signal within parentheses is the initial setting. The description changes depending on
the setting of Pr. 190, Pr. 192 or Pr. 197 "Output terminal function selection". (Refer to section
6.9.5.)
Item
Instruction
Code
Bits
Description
Example
Inverter
status
monitor
H7A
8
b0: RUN (inverter running)
b1: Forward rotation
b2: Reverse rotation
b3: SU (up to frequency)
b4: OL (overload)
b5: —
b6: FU (frequency detection)
b7: ABC (alarm)
Inverter
status
monitor
(extended)
H79
16
b0: RUN (inverter running)
b1: Forward rotation
b2: Reverse rotation
b3: SU (up to frequency)
b4: OL (overload)
b5: —
b6: FU (frequency
detection)
b7: ABC (alarm)
b8: —
b9: SO (Safety monitor
output)
b10 to b14:—
b15: Alarm occurrence
Tab. 6-63:
Monitoring the inverter status
Example 1: H02 (During forward rotation)
Example 2: H80 (Stop at alarm occurrence)
Example 1: H0002 (During forward rotation)
Example 2: H8080 ( Stop at alarm occurrence)
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......