Simple mode parameter list
Basic settings
5 - 6
쑶
I001746E
Fig. 5-4:
Setting the starting torque
NOTES
A too large setting will cause the motor to overheat, resulting in an overcurrent trip (OL
(overcurrent alarm) then E.OC1 (overcurrent shutoff during acceleration)), thermal trip
(E.THM (Motor overload shutoff), and E.THT (Inverter overload shutoff)). When an error
(E.OC1) occurs, release the start command, and decrease the value 1% by 1%. (Refer to
page 7-9.)
If the inverter still does not operate properly after the above measures, adjust the accelera-
tion/deceleration setting or activate the vector control function by Pr. 80 "Advanced magnetic
flux vector control". (Refer to section 6.2.2.)
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Press the MODE key to choose the parameter
setting mode.
Turn the digital dial until P.0 (Pr. 0) appears.
Press the SET key to show the currently set value.
"6.0" (initial value is 6% for 400 V inverters for
motors up to 0.75 kW) appears.
Turn the digital dial to change it
to the setting value of "7.0" (7.0%).
Press the SET key to set.
Operation
Display
The parameter number read previously appears.
Flicker ... Parameter setting complete!
PU indication is lit.
The initial value differs
according to the
capacity.
By turning the digital dial, you can read another parameter.
Press the SET key to show the setting again.
Press the SET key twice to show the next parameter.
PRM indication is lit.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......