Communication operation and settings
Parameter
6 - 202
Stop operation selection at occurrence of communication fault (Pr. 502)
Stop operation when retry count excess (Mitsubishi inverter protocol only) or signal loss detec-
tion error occurs can be selected.
Pr. 502
Operation
Indication
Fault Output
0 (initial value)
Coasts to stop.
E. PUE lit
Provided
1
Decelerates to stop
E. PUE lit after stop
Provided after stop
2
Not provided
Tab. 6-49:
Operation at fault occurrence
Pr. 502
Operation
Indication
Fault Output
0 (initial value)
Kept stopped
E.PUE
Kept provided
1
2
Automatic restart functions
Normal display
Not provided
Tab. 6-50:
Operation at fault removal
Fig. 6-106:
Operation when Pr. 502 setting is "0" (initial
value)
I001834E
Fig. 6-107:
Operation when Pr. 502 setting is "1"
I001835E
Communication
fault
Display
OFF
Fault
occurrence
Output frequency
Fault display
(E.PUE)
Fault output
(ALM)
ON
Fault
removal
Motor
coasting
OFF
ON
OFF
Time
Communication
fault
Display
OFF
Fault
occurrence
Output frequency
Fault display
(E.PUE)
Fault output
(ALM)
ON
Fault
removal
Decelerates
to stop
OFF
ON
OFF
Time
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......