Parameter
Frequency setting by analog input (terminal 2, 4)
FR-D700 SC EC
6 - 155
There are three methods to adjust the frequency setting voltage (current) bias/gain:
●
Method to adjust any point by application of voltage (current) to across the terminals 2-5
(4-5). (Refer to page 6-157.)
●
Method to adjust any point without application of a voltage (current) to across terminals 2-5
(4-5). (Refer to page 6-158.)
●
Adjusting only the frequency without adjusting the voltage (current).
(Refer to page 6-159.)
I001191E
Fig. 6-83:
Signal adjustment of terminal 2
I001191E
Fig. 6-84:
Signal adjustment of terminal 4
NOTE
When voltage/current input signal for terminal 4 was switched using Pr. 267 and voltage/cur-
rent input switch, perform calibration without fail.
Frequency setting signal
Output frequency [Hz]
0
0
0
C3 (Pr. 902)
100%
5V
10V
C4 (Pr. 903)
Gain Pr. 125
Initial value
Bias
50Hz
C2
(Pr. 902)
Frequency setting signal
Output frequency [Hz]
0
0
C6 (Pr. 904)
100%
20mA
C7 (Pr. 905)
Gain Pr. 126
Initial value
Bias
50Hz
C5
(Pr. 904)
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......