Operation selection at power failure
Parameter
6 - 132
If offline auto tuning ended in error (see the table below), frequency search gain are not set. Per-
form an inverter reset and restart tuning.
When tuning is ended forcibly by pressing the STOP-key or turning off the start signal (STF or
STR) during tuning, offline auto tuning does not end properly. (The frequency search gain have
not been set.) Perform an inverter reset and restart tuning.
When using the motor corresponding to the following specifications and conditions, reset Pr.9
"Electronic thermal O/L relay" as below after tuning is completed.
●
When the rated power specifications of the motor is 200/220V (400/440V) 60Hz, set 1.1
times rated motor current value in Pr. 9.
●
When performing motor protection from overheat using a PTC thermistor or motor with
temperature detector such as Klixon, set "0" (motor overheat protection by the inverter is
invalid) in Pr. 9.
Error Display
Error Cause
Remedy
8
Force end
Set "21" in Pr. 96 and perform tuning again.
9
Inverter protective function operation
Make setting again.
91
Current limit (stall prevention) function was
activated.
Set "1" in Pr. 156.
92
Converter output voltage reached 75% of
rated value.
Check for fluctuation of power supply voltage.
93
– Calculation error
– A motor is not connected.
Check the motor wiring and make setting
again.
Set the rated current of the motor in Pr. 9.
Tab. 6-26:
Value of Parameter 96
NOTES
The motor constants measured once in the offline auto tuning are stored as parameters and
their data are held until the offline auto tuning is performed again.
An instantaneous power failure occurring during tuning will result in a tuning error. After
power is restored, the inverter goes into the normal operation mode. Therefore, when STF
(STR) signal is on, the motor runs in the forward (reverse) rotation.
Any alarm occurring during tuning is handled as in the ordinary mode. Note that if an error
retry has been set, retry is ignored.
The set frequency monitor displayed during the offline auto tuning is 0Hz.
Changing the terminal assignment using Pr. 178 to Pr. 182 may affect the other functions.
Make setting after confirming the function of each terminal.
The SU and FU signals are not output during a restart. They are output after the restart
cushion time has elapsed.
Automatic restart operation will also be performed after a reset or when a retry is made by
the retry function.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......