Wiring
Inverter and peripheral devices
FR-D700 SC EC
3 - 3
3.1.1 Peripheral
devices
Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be
selected according to the capacity. Refer to the following list and prepare appropriate peripheral
devices:
Select the MCCB according to the inverter power supply capacity. Install one MCCB per
inverter.
The places with "xx" refer to the breaking capacity in case of short circuit. The correct
selection must be done depending on the design of the power input wiring.
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic
contactor is 500,000 times. When the magnetic contactor is used for emergency stop during
motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side
during commercial-power supply operation, select the MC with class AC-3 rated current for
the motor rated current.
Motor Output
[kW]
Applicable Inverter
Type
Breaker Selection
Input Side Magnetic
Contactor
Reactor Connection
Reactor Connection
Without
With
Without
With
200V class
0.1
FR-D720S-008SC
NF32 xx 3P 6 A
S-N10
0.2
FR-D720S-014SC
0.4
FR-D720S-025SC
NF32 xx 3P 10 A
NF32 xx 3P 6 A
0.75
FR-D720S-042SC
NF32 xx 3P 16 A NF32 xx 3P 10 A
1.5
FR-D720S-070SC
NF32 xx 3P 32 A NF32 xx 3P 16 A
2.2
FR-D720S-100SC
NF32 xx 3P 40 A NF32 xx 3P 32 A
S-N20,S-N21
S-N10
400V class
0.4
FR-D740-012SC
NF32 xx 3P 6 A
S-N10
0.75
FR-D740-022SC
1.5
FR-D740-036SC
NF32 xx 3P 10 A
2.2
FR-D740-050SC
NF32 xx 3P 16 A NF32 xx 3P 10 A
3.7
FR-D740-080SC
NF63 xx 3P 20 A NF32 xx 3P 16 A
5.5
FR-D740-120SC
NF63 xx 3P 32 A NF63 xx 3P 20 A
S-N20, S-N21
S-N11, S-N12
7.5
FR-D740-160SC
NF63 xx 3P 32 A
S-N20, S-N21
S-N20, S-N21
Tab. 3-1:
Breakers and contactors
Fig. 3-2:
Installation of the breakers
I001332E
NOTES
When the inverter capacity is larger than the motor capacity, select an MCCB and a mag-
netic contactor according to the inverter type and cable and reactor according to the motor
output.
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit),
damage to internal parts of the inverter, etc. Identify the cause of the trip, then remove the
cause and power on the breaker.
M
3~
M
3~
Inverter
MCCB
Inverter
MCCB
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......