Parameter
Function assignment of external terminals
FR-D700 SC EC
6 - 95
Fig. 6-48:
2-wire type connection (Pr. 250 = 8888)
I001149E
NOTES
When Pr. 250 is set to any of "0 to 100, 1000 to 1100", the motor coasts to a stop if the start
command is turned off. (Refer to section 6.8.3.)
The STF and STR signals are assigned to the STF and STR terminals in the initial setting.
The STF signal can be assigned to Pr. 178 "STF terminal function selection" and the STR
signal to Pr. 179 "STR terminal function selection" only.
Start signal
Forward/reverse signal
Inverter
Output frequency
Fo
rw
a
rd
rot
a
tion
Re
v
e
rs
e
rotation
Time
ON
ON