Wiring ASDA-A3
3-54
Revision December, 2017
3
When the motor runs normally (Servo On), but one of the safety signal source is low for 1s,
AL501 or AL502 occurs. Then the servo drive is in the Servo Off state.
STO_A
STO_B
S_ON
Servo
status
H
H
L
ON
OFF
Servo on
Servo off & AL501
1 s
L
3.10.5 Related parameter of the STO function
By setting parameter P2.093, you can determine the FDBK status (Pin FDBK+ and FDBK-) and
whether FDBK latches if an STO alarm occurs. The structure for P2.093 is shown below:
P2.093= XX 1
0
(1) (2)(3)
(1)
Not in use
(2)
1: FDBK no latch
2: FDBK latch
(3)
0: Logic A
1: Logic B
2: Logic C
3: Logic D
STO function description:
See the table below. Four logic conditions (Logic A, B, C, and D) are available to standardize the
FDBK status when different STO alarms occur. You can select the corresponding logic according
to the needs of the application. In this table, “Open” means FDBK+ and FDBK- of CN8 are an
open circuit. Take Logic C as an example: when AL500 occurs, FDBK+ and FDBK- of CN8 are
short circuited.
Содержание ASD-A3-0121
Страница 13: ...Revision December 2017 This page is intentionally left blank...
Страница 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Страница 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Страница 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Страница 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Страница 483: ...MODBUS Communication ASDA A3 9 16 Revision December 2017 9 This page is intentionally left blank...
Страница 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Страница 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Страница 603: ...4 Revision December 2017 This page is intentionally left blank...