background image

51.362/1

Sauter Components

AVM 104S…115S: Valve drive with Sauter Universal Technology SUT

For controllers with continuous output (0...10V) or switched output (2- or 3-point control). To operate
through valves or three-way valves in series VXN/BXN, VUD/BUD, VUE/BUE. Choice of characteristic
(linear/equal-percentage) can be set on the actuator.
Two-part housing of fire-retardant plastic, lower part in black, upper part in yellow. With stepping motor,
SUT electronic control unit and maintenance-free gears. Fixing bracket of plastic and cap nut of brass
for fitting the valve. Assembly with the valve is practically automatic. Direction of operation can be
changed at the cable. Electronic, torque-based cut-out via stops on either the actuator or the valve;
automatic adaptation to the valve’s stroke. Coding switches for selecting characteristic and running
time. Disengageable gears for positioning the valve by hand (Allen key enclosed with product). Power
cable 1,2 m long, 5

×

 0,5 mm². Fitting position: anywhere from vertical to horizontal, but not upside down.

Y07552

M

100 %

 0 V    Output signal y        10 V

B07650

0 %

D

irec

tion

 

of

 o

pe

ra

tio

n 2

Di

re

ct

io

n

of o

per

ati

on

 1

Type

Running time

s

Stroke

 

5)

mm

Pushing force

N

Power

Weight

kg

For valves with linear characteristic, can be switched over to equal-percentage

AVM 104S F132

35/65/130

7,5

250

24 V~/=

2)

0,7

AVM 114S F132

60/120

7,5

500

24 V~/=

2)

0,7

For valves with equal-percentage characteristic, can be switched over to linear

AVM 105S F132

35/60/120

8,0

250

24 V~/=

0,7

AVM 115S F132

60/120

8,0

500

24 V~/=

0,7

Positioner

 

1)

Control signal

0...10V, Ri > 100 k

Ω

Starting point U

0

0 or 10V

Positional feedback signal

0...10V, load > 10 k

Ω

Control span 

Δ

U

10V

Switching range X

sh

200 mV

Power supply

24V

±

 20%, 50...60 Hz

Protection (horizontal)

IP 54 as per EN 60529

24V= 

2)

+ 20% / - 10%

Protection class

III as per IEC 60730

Power consumption

AVM 105S F132

4,8 W

8,5 VA

Response time 

1)

200 ms

AVM 115S F132

4,9 W

8,7 VA

Wiring diagram

A09673

Max. media temperature

100 °C

Dimension drawing

M09743

Permissible amb. temp.

–10...55 °C

Fitting instructions 1 . 4S

MV 505790

Ambient humidity

5…95 %rh

Fitting instructions 1 . 5S

MV 506065

without condensation

Declaration on materials

MD 51.362

For control valve type KTM512 / TA-Regulator DN 15…50

Type

Running time

s

Stroke

mm

Pushing force

N

Power

Weight

kg

AVM 115S F901

80/160

10,0

500

24 V~

0,7

Deviation from standard type: inverse scale therefore inverse direction of operation. Adaptor for
control valve available on the valve or from TA-Regulator, stating reference no. 52 757 003.

Accessories

0313529 001*

Split-range unit for setting sequences; to be fitted in separate distribution box as
per MV 505671

0372145 001*

Single auxiliary change-over contacts 

3)

; MV 505795

0372145 002*

Double auxiliary change-over contacts 

3)

; MV 505795

0372249 001*

Intermediate piece required for media temperature >100 °C
(recommended for temperature < 10 °C); MV 505932

0372273 001*

Adaptor for Siemens VVG / VXG 44 and 48 valves; MV 505848

0372286 001

Potentiometer

 

4)

 130 

Ω

; MV 505795

0372286 002

Potentiometer

 

4)

 1000 

Ω

; MV 505795

0372286 003

Potentiometer

 

4)

 5000 

Ω

; MV 505795

0372462 001

CASE Drives PC Tool for configuration of actuators per computer; MV 506101

*)

Dimension drawing or wiring diagram are available under the same number

1)

Also for 2-point or 3-point. depending on type of connection

2)

24V = for input signal of 0...10V only on AVM 1 . 4; on AVM 1 . 5S for all functions.

3)

Fully variable from 0...100%; max. loading 5 (2) A. 24....230V

4)

Only one potentiometer or one set of auxiliary contacts can be fitted to each drive!

5)

Maximum stroke of drive = 10,0 mm

7151362003  03

Содержание AVM Series

Страница 1: ... Switching range Xsh 200 mV Power supply 24V 20 50 60 Hz Protection horizontal IP 54 as per EN 60529 24V 2 20 10 Protection class III as per IEC 60730 Power consumption AVM 105S F132 4 8 W 8 5 VA Response time 1 200 ms AVM 115S F132 4 9 W 8 7 VA Wiring diagram A09673 Max media temperature 100 C Dimension drawing M09743 Permissible amb temp 10 55 C Fitting instructions 1 4S MV 505790 Ambient humidi...

Страница 2: ...own wires In the end positions on hitting a stop in the valve or reaching the maximum stroke or in the event of an overload the electronic motor cut off responds no end switches The direction of the stroke can be changed by swapping the power supply wires over BN BK The unused red and grey wires should not be connected nor should they come into contact with other wires We recommend that you insula...

Страница 3: ...g AVM 104 S 7 5 s 60 s 2 15 s 120 s 4 B10700 On Off On Off On Off On Off 1 2 3 1 2 3 1 2 3 Run time per mm Switch coding Run time for 8 mm stroke factory setting AVM 114S On Off Signal Signal v Signal v Signal v lin v v v Signal Signal On Off On Off B10701 1 2 3 1 2 3 1 2 3 Stroke Desired character curve Switch coding Characteristic curve for valve Characteristic curve for drive Effective on valve...

Страница 4: ...me per mm Switch coding Run time for 8 mm stroke factory setting AVM 115S On Off v v v lin lin v v v On Off On Off B10704 1 2 3 1 2 3 1 2 3 Signal Signal Signal Signal Signal Signal Stroke Stroke Stroke Desired character curve Switch coding Characteristic curve for valve Characteristic curve for drive Effective on valve Stroke Stroke Equal percentage Linear Linear factory setting Stroke AVM 105S A...

Страница 5: ...ing instructions connectors cable 1 2 metres in length and an interface converter for the PC The application is designed for commissioning and service techni cians and for experienced users The last setting i e whether with coding switch or CASE Drives has priority This setting is active when the valve s running time or characteristic is changed via the coding switch To ensure that the settings wi...

Страница 6: ...via an opening with black lid in the housing cover The auxiliary contacts should be screwed onto the drive s top cover Before the mechanical connection can be established the indicator knob should be removed A new indicator is then visible on the lid of the auxiliary contacts N B The housing should not be opened Fitting outdoors If the devices are fitted outdoors we recommend that additional measu...

Страница 7: ...AVM 104S 115S 51 362 7 Sauter Components Wiring diagram 7151362003 03 RD red BN brown BK black BU blue GY grey A10450 ...

Страница 8: ...inal numbers denotes a decimal point Fr Sauter AG CH 4016 Basle 7151362003 03 372145 001 A09782 RD BN BK A10183 RD BN BK GN GY VT 372145 002 372273 M10203 Ø33 Ø26 7 SW30 Ø33 Ø26 5 8 10 10 4 24 15 5 3 2 2 5 Ø8 0372249 001 Ø42 5 15 60 Ø33 Ø8 3 2 10 2 5 55 8 Ø16 Z10214 43 5 35 M09743b 122 107 1 70 46 5 23 5 126 7 63 45 6 32 372145 372286 MM 01 02 03 ...

Отзывы: