51.362/2  

AVM 104S...115S

Sauter Components

Operation

Depending on how it is connected (see wiring diagram). the actuator can be used as a continuous
0...10V. as a 2-point (open/close) or as a 3-point drive (open/stop/close) with intermediate position.
The running time can be matched to requirements using switches S1 and S2 (AVM 105, S1 only). The
characteristic (equal-percentage or linear) can be selected with switch S3. The AVM 104/114 is com-
bined with valves that have a linear basic characteristic such as the VXN and BXN valves. The
AVM 105/115 is combined with valves that have an equal-percentage basic characteristic such as the
VUD. BUD. VUE and BUE valves. The AVM 115 can be fitted on a valve with a linear characteristic (e.g.
VUE 050F200). but you must pay attention to the position of the coding switches. With the AVM 105. it is
not possible to create an equal-percentage characteristic for a valve with a linear characteristic.
Manual adjustment is performed by disengaging the gears (sliding switch next to the power cable) and
simultaneously turning. using an Allen key in the insert on the upper part of the drive. Eight mm of
stroke is attained with 1½ turns.
N.B.: After manual adjustment. re-set the sliding switch (engage the gears).

Connected as a 2-point actuator

Open/close activation can be effected via two wires. Power is applied to the drive via the blue and the
brown wires. On connecting power to the black wire. the valve’s control passage opens. When power
is switched off. the drive goes to the opposite end position and closes the valve.
The unused red and grey wires should not be connected. nor should they come into contact with other
wires. We recommend that you insulate them.

Connected as a 3-point control unit

By connecting power to the wires (brown or black). the valve can be moved to any position. The cou-
pling rod extends and opens the valve if power is applied to the black wire. It retracts and closes the
valve if power is applied to the blue and the brown wires.
In the end positions (on hitting a stop in the valve or reaching the maximum stroke) or in the event of
an overload. the electronic motor cut-off responds (no end switches). The direction of the stroke can be
changed by swapping the power-supply wires over (BN/BK). The unused red and grey wires should not
be connected. nor should they come into contact with other wires. We recommend that you insulate
them.

Connections for control voltage 0...10V

The integrated positioner controls the drive as a function of the controller’s positioning signal y.
Direction of operation 1 (mains power on brown wire): the coupling rod extends and opens the valve
(control passage) as the positioning signal rises.
Direction of operation 2 (mains power on black wire): the coupling rod retracts and closes the valve
(control passage) as the positioning signal rises.
The starting point and the control span are both permanently set. There is a split-range unit available
(as an accessory) for setting partial ranges.
After manual adjustment or in the event of a power failure for longer than 5 minutes, the drive re-
adjusts itself automatically, always with a running time of:
AVM 104

65 s

AVM 114

60 s

AVM 105

35 s

AVM 115

60 s

After power has been applied. the stepping motor moves to the lower stop. connects to the valve spin-
dle and moves to the upper stop in the valve. thereby determining the closed position. Depending on
the control voltage. any stroke between 0 and 8 mm can then be obtained. Thanks to the electronics
unit. no steps can be lost. and the drive needs no periodical re-adjustment. Parallel operation of more
than one drive of the same type is guaranteed.
The feedback signal y0 = 0...10V corresponds to the effective stroke of 0 to 8 mm.
If the control signal (0...10V) is interrupted and direction of operation 1 is connected. the valve closes
fully (0% position).
The valve’s characteristic can be selected using the coding switch. The characteristics can be gener-
ated only if the drive is used as a continuous drive. Other switches enable the running times to be set.
These can be applied irrespective of whether the 2-point. 3-point or the continuous function has been
chosen.

7151362003  03

Содержание AVM Series

Страница 1: ... Switching range Xsh 200 mV Power supply 24V 20 50 60 Hz Protection horizontal IP 54 as per EN 60529 24V 2 20 10 Protection class III as per IEC 60730 Power consumption AVM 105S F132 4 8 W 8 5 VA Response time 1 200 ms AVM 115S F132 4 9 W 8 7 VA Wiring diagram A09673 Max media temperature 100 C Dimension drawing M09743 Permissible amb temp 10 55 C Fitting instructions 1 4S MV 505790 Ambient humidi...

Страница 2: ...own wires In the end positions on hitting a stop in the valve or reaching the maximum stroke or in the event of an overload the electronic motor cut off responds no end switches The direction of the stroke can be changed by swapping the power supply wires over BN BK The unused red and grey wires should not be connected nor should they come into contact with other wires We recommend that you insula...

Страница 3: ...g AVM 104 S 7 5 s 60 s 2 15 s 120 s 4 B10700 On Off On Off On Off On Off 1 2 3 1 2 3 1 2 3 Run time per mm Switch coding Run time for 8 mm stroke factory setting AVM 114S On Off Signal Signal v Signal v Signal v lin v v v Signal Signal On Off On Off B10701 1 2 3 1 2 3 1 2 3 Stroke Desired character curve Switch coding Characteristic curve for valve Characteristic curve for drive Effective on valve...

Страница 4: ...me per mm Switch coding Run time for 8 mm stroke factory setting AVM 115S On Off v v v lin lin v v v On Off On Off B10704 1 2 3 1 2 3 1 2 3 Signal Signal Signal Signal Signal Signal Stroke Stroke Stroke Desired character curve Switch coding Characteristic curve for valve Characteristic curve for drive Effective on valve Stroke Stroke Equal percentage Linear Linear factory setting Stroke AVM 105S A...

Страница 5: ...ing instructions connectors cable 1 2 metres in length and an interface converter for the PC The application is designed for commissioning and service techni cians and for experienced users The last setting i e whether with coding switch or CASE Drives has priority This setting is active when the valve s running time or characteristic is changed via the coding switch To ensure that the settings wi...

Страница 6: ...via an opening with black lid in the housing cover The auxiliary contacts should be screwed onto the drive s top cover Before the mechanical connection can be established the indicator knob should be removed A new indicator is then visible on the lid of the auxiliary contacts N B The housing should not be opened Fitting outdoors If the devices are fitted outdoors we recommend that additional measu...

Страница 7: ...AVM 104S 115S 51 362 7 Sauter Components Wiring diagram 7151362003 03 RD red BN brown BK black BU blue GY grey A10450 ...

Страница 8: ...inal numbers denotes a decimal point Fr Sauter AG CH 4016 Basle 7151362003 03 372145 001 A09782 RD BN BK A10183 RD BN BK GN GY VT 372145 002 372273 M10203 Ø33 Ø26 7 SW30 Ø33 Ø26 5 8 10 10 4 24 15 5 3 2 2 5 Ø8 0372249 001 Ø42 5 15 60 Ø33 Ø8 3 2 10 2 5 55 8 Ø16 Z10214 43 5 35 M09743b 122 107 1 70 46 5 23 5 126 7 63 45 6 32 372145 372286 MM 01 02 03 ...

Отзывы: