ASDA-A3
Troubleshooting
Revision December, 2017
11-23
11
AL069 Wrong motor type
Trigger condition
and causes
Incremental motor does not support the absolute function.
Checking methods
and corrective
actions
1. Check to see if your servo motor has an incremental or absolute
encoder.
2. Check the setting of P2.069 and correctly set the value. Set P2.069 to 0
if your encoder does not use the absolute function.
How to clear the
alarm?
Set P2.069 to 0 and then cycle power on the servo drive.
AL06A Absolute position is lost / Absolute position is not initialized
Trigger condition
and causes
Condition:
1. Motor in use for the first time.
2. Power supply of the servo drive is cut off and the battery is drained, or
the battery has been replaced and the absolute position is lost.
Cause: the motor is used for the first time or the absolute position is lost due
to changing the battery.
Checking methods
and corrective
actions
Check if the absolute position is correctly initialized (see Section 10.3.1).
How to clear the
alarm?
This alarm is cleared after you complete the initialization of the absolute
position.
AL070 Encoder does not complete the command issued by servo drive
Trigger condition
and causes
Command is not completed when the barcode is written to the encoder.
Checking methods
and corrective
actions
Check if the wiring is correct and firmly connected. If not, please correctly
connect the wiring again.
How to clear the
alarm?
Cycle power on the servo drive.
AL072 Encoder overspeed
Trigger condition
and causes
When encoder is powered by the servo drive: over 8800 rpm;
When encoder is powered by the battery: over 10000 rpm.
Checking methods
and corrective
actions
1. Check if the motor is well grounded; make sure the power cable is
grounded to the heat sink of the servo drive.
2. Make sure the encoder cable is separated from the power supply or any
high-current cable to avoid interference.
3. Use shielded cable for the encoder and pull out the shielded mesh and
Содержание ASD-A3-0121
Страница 13: ...Revision December 2017 This page is intentionally left blank...
Страница 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Страница 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Страница 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Страница 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Страница 483: ...MODBUS Communication ASDA A3 9 16 Revision December 2017 9 This page is intentionally left blank...
Страница 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Страница 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Страница 603: ...4 Revision December 2017 This page is intentionally left blank...