SECTION 3 - WIRING GUIDELINES
SECTION 3 - WIRING GUIDELINES
SECTION 3 - WIRING GUIDELINES
SECTION 3 - WIRING GUIDELINES
SECTION 3 - WIRING GUIDELINES
Routing Low-
Voltage Leads
WARNING!
WARNING!
WARNING!
WARNING!
WARNING! Electrical installation should be accomplished only by
experienced service personnel! OTHERWISE, DEATH,
PERSONAL INJURY, OR EQUIPMENT DAMAGE
COULD OCCUR.
When routing low-voltage leads, follow these guidelines:
•
Do not route low-voltage leads in the same conduit as wires
carrying a high-current load.
•
Do not route low-voltage leads adjacent to, or across wires
carrying a high-current load. If low-voltage leads must cross or
run parallel to wires carrying high current, keep the leads at least
6" (152 mm) from high-current wires.
•
Do not splice or solder leads.
•
All wiring should be in conduits or wireways.
WARNING!
WARNING!
WARNING!
WARNING!
WARNING! Electrical connections should be made only by
experienced service personnel! OTHERWISE, DEATH,
PERSONAL INJURY, OR EQUIPMENT DAMAGE
COULD OCCUR.
When connecting the supply of electrical power, follow these guidelines:
•
Connect the control to a “clean” supply of electrical power. Use a
dedicated circuit if possible.
If a dedicated circuit is not available, do
not connect the control to a circuit that
supplies high-amperage equipment—
use another circuit such as a lighting
circuit. Otherwise, equipment may not
function properly.
Connecting the
Supply of
Electrical
Power
Summary of Contents for VC350A
Page 1: ...VC350A Flexoseal System Manual Number MC037 Release Date May 2001 ...
Page 8: ...Section 1 Introduction VC350A Flexoseal System Valco Cincinnati 1 2 Figure 1 1 VC350A Control ...
Page 68: ...Section 9 Maintenance VC350A Flexoseal System Valco Cincinnati 9 9 Figure 9 4 Fluid Regulator ...
Page 133: ...Section 12 Part Number List VC350A Flexoseal System Valco Cincinnati 12 44 400EZ Glue Valve ...
Page 163: ...Section 12 Part Number List VC350A Flexoseal System Valco Cincinnati 12 74 Fittings ...