15.3
Error Code Table
15-17
●
:
Recoverable, -: Unrecoverable
Error
code
Error name
Description
Object
Recovered
Countermeasures
3046H
Movement
automatic check
value error
The difference between the
command value and
feedback value exceeded
the movement automatic
check threshold value with
the movement automatic
check function.
Each
axis
Check the operation of the target
axes.
Check the parameter of the
movement amount automatic
check function.
3050H
Torque
judgment error
The torque value exceeds
the setting torque monitor
judgement value.
Each
axis
- Design the system within the
range that the torque of the
motor does not exceed the
judgment value.
- Check the torque monitor
judgment value.
3051H
Actual speed
judgment value
error
The actual speed exceeds
the setting actual speed
monitor judgement value.
Each
axis
- Design the system within the
range that the actual speed of
the motor does not exceed the
judgment value.
- Check the actual speed
monitor judgment value.
3060H
Home return not
executable error
The home return could not
be executed as AMP
parameter settings and
signal input were not
correct.
Each
axis
Check the parameters of AMP
and signal inputs.
(Note): To simplify the displays, only the lower four digits (Hex) of each error code are displayed in the above table.
Summary of Contents for AFP7MC16EC
Page 1: ......
Page 19: ...1 Unit Functions and Restrictions ...
Page 28: ...Unit Functions and Restrictions 1 10 ...
Page 29: ...2 Names and Functions of Parts ...
Page 33: ...3 Installation and Wiring ...
Page 47: ...4 Basic Procedure ...
Page 75: ...5 Settings of FP7 MC Unit Using CMI Tool ...
Page 97: ...6 Data Transfer to MC Unit and Test Operation ...
Page 122: ...Data Transfer to MC Unit and Test Operation 6 26 ...
Page 123: ...7 Creation of User Programs ...
Page 131: ...8 Automatic Operation Position Control ...
Page 143: ...8 2 Interpolation Control 8 13 ...
Page 193: ...9 Automatic Operation Synchronous Control ...
Page 251: ...10 Manual Operation JOG Operation ...
Page 257: ...10 2 Changing Speed During JOG Operation 10 7 MEMO ...
Page 263: ...11 Manual Operation Home Return ...
Page 277: ...12 Stop Functions ...
Page 286: ...Stop Functions 12 10 ...
Page 287: ...13 Supplementary Functions ...
Page 336: ...Supplementary Functions 13 50 ...
Page 337: ...14 CMTimeChart Monitor ...
Page 338: ...CMTimeChart Monitor 14 2 14 1 Overview of Function ...
Page 365: ...15 Troubleshooting ...
Page 396: ...Troubleshooting 15 32 ...
Page 397: ...16 Specifications ...
Page 500: ...Specifications 16 104 16 13Dimensions AFP7MC16EC AFP7MC32EC AFP7MC64EC 90 28 80 4 Unit mm ...
Page 502: ......
Page 503: ......
Page 504: ......