4.5
Connection of Limit and Near Home Switches
4-25
4.5.4 Settings of FP7 MC Unit
To enable the limit function, the axis parameter "Limit input" in CMI should be set to be
enabled. Also, the input logic should be confirmed on CMI.
Settings related to limit switch
Parameter name
Default
Description
Limit switch
N: Disabled
When using the limit switch function or the home return function
using limit switches, select "A: Enabled".
N: Disabled, A: Enabled
Limit switch
connection
S: Standard
When the arrangement of the connected "limit + switch" and "limit -
switch " is opposite to the input state loaded to FP7 MC Unit, select
"R: Reverse connection".
S: Standard, R: Reverse connection
Limit + switch logic
1: Normal Close
(B contact)
Select the input logic of the limit switches.
0: Normal Open (A contact), 1: Normal Close (B contact)
Limit - switch logic
KEY POINTS
•
In the system using FP7 MC Unit, limit switches are connected to the
general-purpose inputs (SI-MON3 and SI-MON4) of Servo Amplifier A6B/A5B.
When the "Limit switch" is set to "Enabled" in the above parameter, the
state of the general-purpose inputs (SI-MON3 and SI-MON4) of Servo
Amplifier A6B/A5B is reflected as the limit inputs of FP7 MC Unit.
•
It is recommended to select "Normal Open (A contact)" for "Limit + Switch
logic" and "Limit - Switch logic". The input logic selected on Servo
Amplifier A6BA5B is reflected as is.
REFERENCE
•
For details of the axis parameter settings, refer to "5.2 Axis Parameter
Settings".
Summary of Contents for AFP7MC16EC
Page 1: ......
Page 19: ...1 Unit Functions and Restrictions ...
Page 28: ...Unit Functions and Restrictions 1 10 ...
Page 29: ...2 Names and Functions of Parts ...
Page 33: ...3 Installation and Wiring ...
Page 47: ...4 Basic Procedure ...
Page 75: ...5 Settings of FP7 MC Unit Using CMI Tool ...
Page 97: ...6 Data Transfer to MC Unit and Test Operation ...
Page 122: ...Data Transfer to MC Unit and Test Operation 6 26 ...
Page 123: ...7 Creation of User Programs ...
Page 131: ...8 Automatic Operation Position Control ...
Page 143: ...8 2 Interpolation Control 8 13 ...
Page 193: ...9 Automatic Operation Synchronous Control ...
Page 251: ...10 Manual Operation JOG Operation ...
Page 257: ...10 2 Changing Speed During JOG Operation 10 7 MEMO ...
Page 263: ...11 Manual Operation Home Return ...
Page 277: ...12 Stop Functions ...
Page 286: ...Stop Functions 12 10 ...
Page 287: ...13 Supplementary Functions ...
Page 336: ...Supplementary Functions 13 50 ...
Page 337: ...14 CMTimeChart Monitor ...
Page 338: ...CMTimeChart Monitor 14 2 14 1 Overview of Function ...
Page 365: ...15 Troubleshooting ...
Page 396: ...Troubleshooting 15 32 ...
Page 397: ...16 Specifications ...
Page 500: ...Specifications 16 104 16 13Dimensions AFP7MC16EC AFP7MC32EC AFP7MC64EC 90 28 80 4 Unit mm ...
Page 502: ......
Page 503: ......
Page 504: ......