Manual
Operation
(JOG Operation)
10-12
10.4.2 Precautions on Programming
Precautions on programming
•
If any value such as an inching movement, acceleration time, deceleration time or target
speed is out of the specified range, a setting value error will occur at the time of startup.
•
Unit memory numbers allocated to flags and start requests vary depending on axis numbers.
•
A specified slot number varies depending on the installation position of the unit.
Operation at Over limit input (Limit is valid)
Condition
Direction
Limit status
Operation
When JOG
operation is started
Forward
Over limit input (+): ON
Not executable, Error occurs.
Over limit input (-): ON
Executable
Reverse
Over limit input (+): ON
Executable
Over limit input (-): ON
Not executable, Error occurs.
During JOG
operation
Forward
Over limit input (+): ON
Deceleration stop, Limit error occurs.
Reverse
Over limit input (-): ON
Deceleration stop, Limit error occurs.
Operation when an error occurs
The operation of FP7 MC Unit when an error occurs varies according to the "MC common
settings" of FP7 MC Unit and the "CPU Configuration" of the CPU unit. Note that the JOG
operation may be restarted depending on the settings and execution conditions.
Example) When the execution condition for JOG is on, the operation is restarted:
Condition
Unit
Setting method
Parameter name
Setting
example
①
FP7 MC Unit
CMI: MC common settings
Operation when an error
occurs
All axes stop
②
ⓐ
FP7 MC Unit
CMI: MC common settings
Error alarm to CPU unit
No
②
ⓑ
FP7 MC Unit
CMI: MC common settings
Error alarm to CPU unit
Yes
CPU unit
FPWIN GR7:
FP7 Configuration > CPU
Configuration
Operation when unit error
occurs
Operation
continues.
When the setting is like the condition (1), when an error occurs during the JOG operation,
normal axes stop once. However, when the setting is like the condition (2) (a) or (2) (b), if the
JOG operation request is on, the JOG operation will start again after the stop. If such an event
needs to be avoided, add error annunciation flags of other axes as interlock release signals.
Summary of Contents for AFP7MC16EC
Page 1: ......
Page 19: ...1 Unit Functions and Restrictions ...
Page 28: ...Unit Functions and Restrictions 1 10 ...
Page 29: ...2 Names and Functions of Parts ...
Page 33: ...3 Installation and Wiring ...
Page 47: ...4 Basic Procedure ...
Page 75: ...5 Settings of FP7 MC Unit Using CMI Tool ...
Page 97: ...6 Data Transfer to MC Unit and Test Operation ...
Page 122: ...Data Transfer to MC Unit and Test Operation 6 26 ...
Page 123: ...7 Creation of User Programs ...
Page 131: ...8 Automatic Operation Position Control ...
Page 143: ...8 2 Interpolation Control 8 13 ...
Page 193: ...9 Automatic Operation Synchronous Control ...
Page 251: ...10 Manual Operation JOG Operation ...
Page 257: ...10 2 Changing Speed During JOG Operation 10 7 MEMO ...
Page 263: ...11 Manual Operation Home Return ...
Page 277: ...12 Stop Functions ...
Page 286: ...Stop Functions 12 10 ...
Page 287: ...13 Supplementary Functions ...
Page 336: ...Supplementary Functions 13 50 ...
Page 337: ...14 CMTimeChart Monitor ...
Page 338: ...CMTimeChart Monitor 14 2 14 1 Overview of Function ...
Page 365: ...15 Troubleshooting ...
Page 396: ...Troubleshooting 15 32 ...
Page 397: ...16 Specifications ...
Page 500: ...Specifications 16 104 16 13Dimensions AFP7MC16EC AFP7MC32EC AFP7MC64EC 90 28 80 4 Unit mm ...
Page 502: ......
Page 503: ......
Page 504: ......