Creation
of User Programs
7-8
7.3 Precautions on Programming
7.3.1 Turning Off Power Supply Clears Contents in Unit Memories
•
Data in unit memories are cleared when the power is turned off.
•
When the power is turned on again, data is preset in the parameters saved in the FROM
within FP7 MC Unit.
7.3.2 Operation Cannot be Switched Once One Operation Has Started
•
If any of the startup requests for position control, synchronous control, JOG operation and
home return turns on and the operation is initiated, this operation cannot be switched to
another operation even if another request turns on.
•
BUSY flags corresponding to each axis turn on during operation. Insert them as interlock
signals for each start request on user programs.
•
The stop operations (system stop, limit stop, error stop, emergency stop and deceleration
stop) are preferentially activated even in other operations.
7.3.3 Operation When PLC Mode Changes from RUN to PROG.
The operation when the mode of the CPU unit changes from RUN to PROG. varies depending
on the setting of “RUN > PROG operation” of “MC common settings”.
MC common settings
Parameter
name
Default
Description
RUN->PROG.
operation
Deceleration
stop
Set the operation of FP7 MC Unit when the mode of CPU unit changes
from RUN to PROG.
Operation
continuance
The operation of each axis continues.
Deceleration
stop
Each axis decelerates and stops in a specified
deceleration stop time in the current control mode.
Immediate
stop
Each axis decelerates and stops in a specified emergency
stop deceleration time.
Summary of Contents for AFP7MC16EC
Page 1: ......
Page 19: ...1 Unit Functions and Restrictions ...
Page 28: ...Unit Functions and Restrictions 1 10 ...
Page 29: ...2 Names and Functions of Parts ...
Page 33: ...3 Installation and Wiring ...
Page 47: ...4 Basic Procedure ...
Page 75: ...5 Settings of FP7 MC Unit Using CMI Tool ...
Page 97: ...6 Data Transfer to MC Unit and Test Operation ...
Page 122: ...Data Transfer to MC Unit and Test Operation 6 26 ...
Page 123: ...7 Creation of User Programs ...
Page 131: ...8 Automatic Operation Position Control ...
Page 143: ...8 2 Interpolation Control 8 13 ...
Page 193: ...9 Automatic Operation Synchronous Control ...
Page 251: ...10 Manual Operation JOG Operation ...
Page 257: ...10 2 Changing Speed During JOG Operation 10 7 MEMO ...
Page 263: ...11 Manual Operation Home Return ...
Page 277: ...12 Stop Functions ...
Page 286: ...Stop Functions 12 10 ...
Page 287: ...13 Supplementary Functions ...
Page 336: ...Supplementary Functions 13 50 ...
Page 337: ...14 CMTimeChart Monitor ...
Page 338: ...CMTimeChart Monitor 14 2 14 1 Overview of Function ...
Page 365: ...15 Troubleshooting ...
Page 396: ...Troubleshooting 15 32 ...
Page 397: ...16 Specifications ...
Page 500: ...Specifications 16 104 16 13Dimensions AFP7MC16EC AFP7MC32EC AFP7MC64EC 90 28 80 4 Unit mm ...
Page 502: ......
Page 503: ......
Page 504: ......