 RE - 104 
     

        

 

 

 
 
 

 

Fire Alarm Control Panel 

 
 
 
 

 

Installation, Commissioning &

 

Operating 

Manual

 

 

 
 

 

 

 
 
 
 

Summary of Contents for RE - 104

Page 1: ...RE 102 RE 104 Fire Alarm Control Panel Installation Commissioning Operating Manual ...

Page 2: ...P N RE 102 104 Rev No 0 1 ...

Page 3: ...P N RE 102 104 Rev No 0 2 ...

Page 4: ...P N RE 102 104 Rev No 0 3 NOTES ...

Page 5: ...ER 3 Installation 11 3 1 Installation Precaution 11 3 2 Mounting Details 13 3 3 Input Circuits 14 3 4 Output Circuits 15 CHAPTER 4 Operating Instructions 16 4 1 Switch Functions 16 4 2 Status LED 17 4 3 Operation 18 4 3 1 Zone Fault Response 18 4 3 2 Zone Fault Restoral 18 4 3 3 Zone Fire Response 18 4 3 4 Zone Fire Restoral 18 4 3 5 programming Menu Flow Chart 19 CHAPTER 5 Servicing 20 5 1 Walk t...

Page 6: ...sitions of the field devices and the control equipment 1 2 General The panel is self contained with integral power supply and space provision for two sealed lead acid standby batteries and comply with the requirements of IS 2189 1999 The panel functions are microprocessor controlled and test and isolate functions are included Provision is made for a repeater function of panel status output The pan...

Page 7: ... the audible alarms and resetting the system as described later Fault Indication If the control panel indicates a Fault condition make a note of all illuminated indicators refer to the chart on Page 23 and call the service engineer 1 4 User Responsibility In addition to the routine testing described on routine test the user has a responsibility for ensuring certain actions are taken following a fi...

Page 8: ...one tested each week Record and report any malfunction Quarterly The responsible person should ensure that every three months the system is checked by a competent person Check the standby batteries and the charger voltage Test at least one device in each zone to check the panel functions Check the operation of the audible alarms and any link to a remote manned centre Central Station etc Carry out ...

Page 9: ...C voltage and Battery level 2 1 Product Features Rugged CRCA sheet with powder coated finish Operates on 220v 50Hz AC supply Standby battery back up with built in charging Error free Fire Fault status in unambiguous colored LED indication Switch Mode Power Supply 16 X 2 LCD Display Tactile key pad for easy operation Main Standby status indication Low Battery visual warning with audible tone Zone w...

Page 10: ...ss B wiring Normal Operating Voltage Nominal 24 VDC Alarm Current 15 35mA threshold Short Circuit Current 42mA Maximum Loop resistance 50 ohms Maximum End Of Line Resistor 4 7K 1 4watt Standby Current 6 8mA 2 4mA for Detectors Notification Appliance Circuits Sounder Circuit Class B wiring Operating Nominal Voltage 24 VDC Hooter NACs output 1A End Of Line Resistor 4 7K 1 4watt Three Form C Relays R...

Page 11: ... Yellow Zone Fire Red Zone Fault Yellow Zone Isolate Walktest Yellow Local Buzzer A piezo buzzer provides separate and distinct sounds for alarm and trouble conditions Alarm steady Fault pulse 0 5sec ON and 0 5sec OFF 2 3 2 Controls SILENCE Key During fire fault condition silence key is used to silence the external Sounders NAC and the internal buzzer tone ...

Page 12: ...ccept the changes of edited menu This key also used for lamp test in system normal condition MENU Key This key is used to enter into the Main menu in the LCD 2 4 Mechanical Construction The enclosure of the Panel is constructed by CRCA sheet with powder coated finish and it s designed to afford the degree of protection as per IP 54 The 19mm knock outs are given for cable entry at the top of the ca...

Page 13: ...r any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions known to be affected by a change must be 100 tested In addition to ensure that other operations are not inadvertently affected at least 10 of initiating devices that are not directly affected by the change...

Page 14: ...mage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduc...

Page 15: ...d the inner parts of the panel are given sufficient protection during installation All external cables are to be entered via the 19mm preformed knockouts located at the top of the panel When the installation of all the cables has been completed clean the interior of the enclosure ensuring all masonry debris and drilling swords are removed 30 mm 290 mm 30 mm 175 mm 35 mm 185 mm ...

Page 16: ... zone is supervised for opens and ground faults Both conditions are visually and audibly toggle tone annunciated Each zone is a Class B Initiating Device Circuit IDC Zones designed to accept any normally open contact devices and conventional 2 wire 24 volt smoke detectors It is allowable to mix an assortment of device types i e smoke detectors heat detectors pull stations etc on any zone Zone Circ...

Page 17: ...total load capacity of this circuit is capacity of this O P is 1Amps Sounder Circuit Class B Note If the non polarized devices are used connect the device as mentioned in page 23 Standard Relay The control panel provides three Form C relays 2 for Fire 1 fro Fault rated for 2 0 amps 30 VDC and 2 0 amps 30 VAC Relay connections are power limited ...

Page 18: ...y Fire Condition The panel is reset by pressing this key followed by password if enabled During reset condition all the detector input voltages are cut off up to 3 seconds for Detectors and MCP s Then voltages are put on to the loop ENTER Key This key is used to check the all LED s in panel is in good condition with continuous buzzer tone in normal operating condition The same key is used to accep...

Page 19: ...e blown the AC Power on LED will OFF and it also indicated by fault Buzzer tone BATTERY ON This LED indicates the presence of standby power supply Whenever the Main Supply 220v A C fails the panel supply is switched to standby power supply with BATTERY ON indication Whenever the backup battery fails fuse blown the battery fail is indicated by LCD with fault Buzzer tone Note Whenever the backup bat...

Page 20: ... corresponding ZONE FIRE red LED will be illuminated At the same time hooter potential free contact Fire Relay and local buzzer continuous tone will be activated The External hooter NAC Sounder and buzzer will be silenced by using the Silence Key and silenced LED indicates it Always the recent fired zone FIRE LED will blink continuously rest of the fired zone FIRE LED s will glow constantly till i...

Page 21: ...rease the time delay 1 Zone 1 1 Zone 1 Enabled 1 Zone 1 Disabled 1 Zone 1 Zone Test 1 Zone 1 Walk Test Default 2 Zone 2 3 Zone 3 4 Zone 4 5 Auto KeyLock Ena bled 5 Auto KeyLock Disabled 7 Auto Silence Enabled 7 Auto Silence Disabled Enter Old Password XXX Ente r New Pa ssword XXX Password Changed Note 1 Use Cursor key to move the menu list previous or next and to interchange the status of the menu...

Page 22: ...zone is Tested for Fire Open Short and Isolate automatically without disturbing the normal operations Walk test Mode In this mode the selected zone is used to check all the loop devices manually one by one The signal from the Initiating device will cause the panel in the alarm mode The panel automatically get silenced and reset after a specific period without activating the fire relay In this mode...

Page 23: ...st the panel comes out of the walk test mode automatically d During test condition that the other zones that are not in test mode fire will consider as actual fire 4 3 5 2 Zone 2 From this menu the zone 2 loop can configured as enable disable Zone test and Walk test The default option is Enable To change the options press Enter key then change the options by using the left right cursor keys The Sc...

Page 24: ...matically and after the set time delay key pad will be locked 4 3 5 6 Auto Lock Time The Auto key lock time will be enabled only when the Auto Key lock is Enabled If the Auto Key Lock is in Enabled condition then by pressing the Enter key from this menu the key lock time can be changed by using the Left Right keys The default factory setting option is disabled and default set time is 60 Seconds 4 ...

Page 25: ...time is 60 Seconds 4 3 5 9 Change Password From this menu the password used for key panel enable can be changed The default factory setting password is 123 The password should be three digits 4 3 5 10 Net Address From this menu the network address used for network panel can be changed The default factory Net work address is 1 The network address can changed by pressing Enter key from this menu it ...

Page 26: ...testing of devices by a single person In this mode if the panel detects any fire then after 3 seconds the panel will get automatically silenced After 6 seconds of silence the panel will go to reset This reset is done for only that particular zone Once in Walktest Mode the control panel will immediately Disable the fire relay Display all alarm conditions as they occur Display all zone troubles as t...

Page 27: ...s the menu key zone1 selects first 2 Press cursor key consequently until select the zone which is to be test 3 After selecting the zone press the ENTER KEY 4 After the ENTER KEY is pressed Select the Zone Test using the cursor key then press enter key Open Short Fire test is Performed for that particular zone Once the testing procedure is finished the previous conditions of the panel are retained ...

Page 28: ...efer specification Page 10 for Quiescent standby alarm currents System current S Quiescent Current Standby current X No of zone Fire current F Alarm Current x no of zones Hooter Current x No of Hooter Example 4 Zone with 48 Hrs in normal condition 1 Hr in Alarm condition S 0 060A 0 0068A X 4 0 0872A F 0 035A X 4 0 2 X 4 no of sounder 0 94A X S 0 0872A x 48 Hrs 4 1856 Y F 0 94A x 1 Hrs 0 94 AH X Y ...

Page 29: ... Total zone loop current exceed the rated value Check number of detectors connected in the loop Total detectors current should not go above 3mA Hooter fault indication There is no proper connection in the hooter Or loop Fault Connection Details for Non Polarized Hooter Diode IN4007 If there is no hooter connected to the output check if EOL resistor connected there or not Check loop wiring for shor...

Page 30: ...P N RE 102 104 Rev No 0 29 Chapter 8 Terminal Details ...

Page 31: ... 044 4204 9599 Email marketing ravelfirepanels com Web www ravelfirepanels com DATE TEST CERTIFICATE This is to certify that the following items are tested and checked Microprocessor Based Conventional Fire Alarm Control Panel Model No RE 102 RE 104 Serial No No of zones 2 Zone 4 Zone For RAVEL ELECTRONICS PVT LTD Q C Engineer Tested By ...

Page 32: ... warranty period returned to the company under a written intimation and which to the company s satisfaction to be found defective The company reserves the right to decide the workplace for the repair work The freight for defective material will have to be borne by the purchaser and the transit risk for such material will rest with the purchaser This warranty will last for a period of 12 months fro...

Page 33: ...P N RE 102 104 Rev No 0 32 Ravel Electronics Pvt Ltd 150A Electronic Industrial Estate Perungudi Chennai 600096 India Web www ravelfirepanels com Email marketing ravelfirepanels com ...