P/N RE - 102 / 104 Rev. No. 0
19
4.3
Operation
4.3.1
ZONE FAULT RESPONSE:
When faults like Open/ Short occurred in the loop, the
corresponding ZONE FAULT LED would identify it.
Note: During the above fault conditions, apart from the
specific fault identification LED, common fault relay and
Local buzzer with intermittent tone will be activated. During
this time, if ‘SILENCE.’ is activated, intermittent tone will be
silenced.
4.3.2
ZONE FAULT RESTORAL:
When the faults condition of the FAP is restored, then the
corresponding fault LED goes off and also common fault relay and
intermittent buzzer tone is deactivated.
4.3.3
ZONE FIRE RESPONSE:
When the control panel detects Fire via the Detector / MCP, the
corresponding ZONE FIRE red LED will be illuminated. At the same
time hooter, potential free contact (Fire Relay) and local buzzer
(continuous tone) will be activated.
The External hooter (NAC / Sounder) and buzzer will be silenced by
using the Silence Key and silenced LED indicates it.
Always the recent fired zone FIRE LED will blink continuously, rest of
the fired zone FIRE LED’s will glow constantly till it goes to RESET. The
FIRE LED indication will remain ON condition till the panel is RESET.
4.3.4
ZONE FIRE RESTORAL:
The control panel returns to normal after all alarms have been
cleared and a system reset key has been pressed followed by the
password if enabled. The control panel will perform the following upon
restoral of all active alarms, The Zone Fire LED, Hooters, buzzer and fire
relay are turn off.
Note:
1.
The Fire relay will be in ON condition till the fire and fault
LED’s go OFF.